Laserfiche WebLink
PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> CGRS <br /> SOLUTIONS DELIVERED <br /> Date: ovo2/18 Work Order# <br /> Location: United Pacific#5447 Contact: Tom M.Robins <br /> 1469 East Hammer Lane <br /> Stockton, CA 95210 Telephone: (310)323-3992 ext.#2012 <br /> SUMP# #7-8 #7-8 #7-8 #7-8 <br /> PRODUCT T-1 91 T-2 89 T-3 87 T-4 Diesel <br /> LD TYPE Mechanical PLLD (P)LLD I M M M M <br /> LD MANUFACTURER VMI VMI VMI VMI <br /> LD MODEL LD-2000 LD-2000 LD-2000 LD-2000 <br /> LD SERIAL NUMBER 18011125 09041087 15031247 07081287 <br /> SUMP CONDITION Dry D Dry Dry <br /> RESILIENCY 150m1 150ml 175ml 140ml <br /> OPERATING PRESSURE 26 si 26psi 26psi 28psi <br /> OPENING TIME 4 seconds 4 seconds 6 seconds 5 seconds <br /> METERING PRESSURE lopsi lops! lopsi lops! <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 18 si 18psi 18psi 18 si <br /> LEAK RATE LD DETECTED 39ph 39ph 3gph 3gph <br /> DOES LD DETECT 3 GPH LEAK RATE? Yes Yes Yes Yes <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A N/A N/A <br /> LD PASS OR FAIL? Pass Pass Pass Pass <br /> Comments: <br /> T-1 91 LD failed 3gph leak testing,one single adjustment was made and retest passed. <br /> Technician: RICHARD THOMAS Contractor Lic. # 803616 <br /> Signature: ��--- -�---;� <br />