JANUARY 4, 1991 <br />BARGHAUSEN CONSULTING ENGINEERS, INC. <br />4612 ROSEVILLE ROAD, SUITE #103 <br />NORTH HIGHLANDS, CA 95660 <br />ATTN: PAUL WILTON <br />RE: ARCO FACILITY 10548 (JOB #3566) LOCATED AT 1612 W. HAMMER <br />LANE, STOCKTON, CA <br />I HAVE REVIEWED THE INSTALLATION PLAN YOU SUBMITTED FOR THE ABOVE <br />REFERENCED FACILITY AND FOUND THE FOLLOWING DEFICIENCIES: <br />1— YOU NEED TO INDICATE THE SPECIFIC U.L LISTED PIPING THAT WILL <br />BE USED FOR BOTH PRIMARY AND SECONDARY CONTAINMENT. <br />2— YOU NEED TO INDICATE WHICH RONAN SENSORS WILL BE USED IN THE <br />ANNULAR SPACE OF EACH TANK AS WELL AS THE SUMP AREA OF EACH <br />TANK. <br />3— YOU NEED TO INCLUDE A BALL CHECK ON THE PHASE I VAPOR RECOVERY <br />FILL PIPE OR DOUBLE CONTAIN AND CONTINUOUSLY MONITOR IT. <br />4— YOU NEED TO PROVIDE A DRAWING SPECIFICALLY INDICATING WHERE THE <br />ANNULAR SPACE MONITOR WILL BE FOR THE DOUBLE WALL FIBERGLASS <br />TANKS (NOT THE STEEL TANKS). <br />5— YOU NEED TO INDICATE WHAT TYPE OF OVERFLOW PROTECTION WILL BE <br />USED. YOU MUST USE A LIQUID LEVEL SENSOR WITH EITHER AN <br />AUTOMATIC SHUTOFF DEVICE (OPW 61 SO) OR AN ALARM TRIGGERED BY <br />THE LIQUID LEVEL SENSOR. <br />6— YOU NEED TO PROVIDE THE SPEC SHEETS FOR THE OVERFILL BOX THAT <br />WILL BE USED, WE DO NOT HAVE THEM IN THIS OFFICE. <br />7— YOU NEED TO SPECIFY WHICH FLEX PIPING WILL BE USED, TELEFLEX OR <br />TITELFLEX. <br />8— NO MONITORING PLAN WAS SUBMITTED, PLEASE HAVE FACILITY SUBMIT <br />ONE (I HAVE INCLUDED THE STATE REQUIREMENTS FOR THE MONITORING <br />PLAN WITH THIS LETTER). <br />9— THE RESPONSE PLAN WAS INADEQUATE, PLEASE BE SPECIFIC WHEN <br />ADDRESSING THE FOLLOWING ITEMS IN THE RESPONSE PLAN: <br />A) A DESCRIPTION OF THE PROPOSED METHODS AND EQUIPMENT TO BE <br />USED FOR REMOVING THE HAZARDOUS SUBSTANCE, INCLUDING THE <br />LOCATION AND AVAILABILITY OF THE REQUIRED EQUIPMENT, IF NOT <br />PERMANENTLY ON SITE, AND AN EQUIPMENT MAINTENANCE SCHEDULE <br />FOR THE EQUIPMENT LOCATED ON—SITE.* <br />