SWRCB;January 2002 Page of <br /> 7. UNDER-DISPENSER CONTAINMENT DC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> UDC#1&2 UDC#3&4 UDC#5&6 UDC#7&8 <br /> rUDCDepth: <br /> facturer: APT APT APT APT <br /> ial: Pot Plastic PolyPlastic PolyPlastic Pol Plastic <br /> 29" 29" 27" 27" <br /> Height from UDC Bottom to Top 15" 15" 14" 15" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 7" 8" 6" 8" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested Water Line 17" Water Line 18 '/2" Water Line 16" Water Line 17" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both X Yes No ❑NA X Yes No ❑NA X Yes No ❑NA X Yes No ❑NA <br /> product and water)?` <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail- X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA <br /> safe shutdown?` <br /> Was fail-safe verified to be <br /> operational?' <br /> fail-safe ❑Yes X No ❑NA ❑Yes X No ❑NA ❑Yes X No ❑NA ❑Yes X No ❑NA <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 11:00 10:50 10:35 10:25 <br /> Initial Reading(Rj): .001 .001 .001 .001 <br /> Test End Time: 11:30 11:20 11:05 10:55 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading RF-RI): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Resalts <br /> ....�, .. � . .:X,Vass ,,,n F�iI� .,,X�Pass.,' Cl;]Cail X,Pass`:;.. CI Fail ,, .::' X..-Pass: ❑Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA <br /> Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes 0 No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />