Laserfiche WebLink
99 LD -2000 0 0 Page 3 of 4 <br />In the early 1990's, the first commercially successful flexible pipe, Total Containment PP -1500, was introduced to the U. S. <br />petroleum industry. Due to the flexibility of this pipe system, no line leak detection would work. In 1992, the Vmi LD -2000\E <br />was certified for 3 GPH @ 10 PSI on Total Containment PP -1500 pipe. The 99 LD -2000\E is still required for existing PP -1500 <br />pipe. Additionally, today the 99 LD -2000\E is used in sites that have the same line characteristics as the LD -2000\E was <br />originally certified for, even though the pipe is different. The original certification of the LD -2000\E concerned the bleed -back <br />modulus of PP -1500 pipe. Today, lines with high bleed -back (generally above 600 ml.) and high head pressure may require <br />the 99 LD -2000\E to pass a field test for annual certification. Consult with factory before ordering and installing the 99 LD -2000 <br />\E. <br />Electronic Line Leak Detection Upgrade! <br />The 99 LD -2000 may be upgraded in the field to eliminate thermal induced slow -flow, provide submersible shut -down, and <br />alarm notification to site monitoring equipment. Request information on the ISM -4080, an easy upgrade for existing or new <br />installations. The ISM4080 also stages turbines and controls solenoid valves for loading racks and marine applications. If <br />there is no need for staged turbines, solenoid valve control, alarm notification or submersible shut -down, request information <br />on the ARM -4073 to eliminate false alarms only. <br />Press Image for a Larger View <br />Fuels: <br />• Gasoline, 100% methanol*, 100% ethanol*, up to 15% MTBE <br />• Any combination of the above <br />• #1 or #2 diesel, kerosene, Jet A* or JP -4*, AV Gas* and Biodiesel* (all blends). <br />When used with Biodiesel, any alcohol fuel concentration above 20%, Jet A, JP -4 or AV Gas, order part # LD2-SSVS for stainless steel fittings <br />and stainless steel vent tubing. For chemical applications other than those listed above, contact factory. <br />Certified to meet EPA 3 GPH @ 10 PSI: <br />• Maximum Rigid Pipeline size: 400 feet of 3.25 inch diameter line or up to 172 gallon volume <br />• Maximum Flexible Pipeline size: 415 feet of 1.5 inch diameter line or up to 39.5 gallon volume <br />U.L. Recognized Containment Housing: <br />• For pump pressures through 50 PSI <br />• Schedule 40 cast iron with zinc phosphate protection <br />• Externally finished with oven baked powder coat <br />Check Valve: <br />• Acetron GP <br />• Viton F Seal <br />Pressure Relief: <br />• Stainless Steel, 29 PSI pressure relief. This pressure is in addition to the pump pressure relief. <br />Seals: <br />• Piston / Poppet: Teflon, stainless steel spring energized <br />• O Rings: U.L. Approved V9702-Viton Type B Fluorocarbon <br />Metering Pin and Poppet: <br />• 17-4 Stainless Steel <br />Misc. Component Specification: <br />• 2011-T3 Aluminum, anodized <br />• 6061-T6 Aluminum, anodized <br />• 1026 cold roll steel, chrome plated <br />• Acetron GP <br />Reverse Ratio Piston -Poppet <br />One -Way Poppet Flow -Path <br />For Installation with variable or non -variable speed turbines. <br />http://www.vaporless.com/vmi website links/products/products_ld2000.htm 1/27/14 <br />