Laserfiche WebLink
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specib) <br />Test Equipment Used: Ineon <br />Sump Tester Equipment Resolution: +/-0.002" <br />Bucket Diameter: <br />Vapor Spill Box # 87 <br />Vapor Spill Box # 91 <br />ve ME <br />12" <br />12" <br />Bucket Depth: <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />Test Start Time: <br />9:44 am <br />1.0:11 am <br />Initial Reading (R,): <br />6.7074 <br />4.0973 <br />Test End Time: <br />9:59 am <br />10:26 am <br />Final Reading (RF): <br />6.7078 <br />4.0972 <br />Test Duration: <br />15 min. <br />15 min. <br />Change in Reading (RF -R,): <br />0.0004 <br />0.0001 <br />Pass/Fail Threshold or <br />Criteria: <br />+/_0.002„ <br />+/_0,002" <br />Test Result: jj <br />IK Pass ❑ Fail <br />® Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />a <br />I V. <br />-04 s <br />ENVIRONMENTAL I <br />Orm-rff twiEH4 <br />