Laserfiche WebLink
Triangle Environmental, Inc. <br />T.E.I. SYSTEMS TANI,LINE AND LEAK DETECTOR TEST REPORT <br />Facility: QUIKSTOP #00138 <br />Tank #. <br />J <br />3 <br />Work #: <br />TC000138 <br />Product: <br />Unleaded Premium <br />Test Date: <br />6/18/2002 <br />Test Method: N/A <br />Capacity: 7950 <br />Diameter (in): <br />Product Level (in): <br />Liquid Volume (Gals): <br />Liquid Percent (%): <br />Specific Gravity: <br />Coef. of Expansion: <br />Water On Tank (in): <br />Water In Tank (in): <br />Product Temp. (F): <br />Head Pressure (psi): <br />Test Start Time: <br />Test End Time: <br />Test Rate (gph): <br />Test Result: N/A <br />Test Method: ULLAGE <br />UllageVolume (gals.): <br />Ullage Test Time: <br />Ullage Vacuum (psi): <br />Ullage Result: N/A <br />Test Method: <br />TEI LT -3 <br />Test Method: <br />R.J. FTA <br />Manufacturer: <br />Vaporless <br />L/D Model: <br />LD2000 <br />L/D Serial #: <br />8328 <br />Line Drain Back (ml): <br />50 <br />L/D Trip Time (sec): <br />2 <br />Holding Pressure (psi): <br />26 <br />Metering Pressure (psi): <br />12 <br />L/D Test Rate (gph): <br />2.9 <br />L/D Result: <br />PASS <br />Test Method: <br />TEI LT -3 <br />Pump Brand: <br />Red Jacket <br />System Type: <br />Pressure <br />Line Pressure (psi): <br />50 <br />Line Start Time: <br />1:00 PM <br />Line End Time: <br />1:15 PM <br />Line Start Level: <br />320 <br />Line End Level: <br />310 <br />Line Test Rate (gph): <br />0.011 <br />Line Test Result: <br />PASS <br />4 <br />