Laserfiche WebLink
` <br />.. <br />0 2002 Walton Engineering, Inc. <br />Product Stored <br />Gasoline - 87 <br />Gasoline - 89 <br />electrical Denetration <br />of sump prior to testing <br />Wet <br />Dry <br />Dry <br />Portion of sump tested <br />Entire <br />Entire <br />Entire <br />Is system programed for fail-safe operation? <br />Yes <br />Yes ... ..... <br />`Was fail-safe verified to be operational? <br />No <br />No <br />No <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Wait time for water level to stabilize (hr:min) <br />0:12 <br />0:15 ....... <br />0:08 <br />Depth of water level from tank top (inches) <br />V. ........ <br />81. <br />Test start time <br />11:21 AM <br />11:20 AM <br />11:22 AM <br />Change in water level 0.000 inches) <br />0.000 <br />0.005 <br />0.005 ..... <br />FAIL Leak <br />FAIL Leak <br />0 2002 Walton Engineering, Inc. <br />