Laserfiche WebLink
E <br />IINE LEAK DETECTOR (LLD) TEST REPORT,,,,, <br />TEST DATE: August 09, 2017 <br />Al. FACILITY <br />Name Quik Stop Market #138 <br />Address 1153 Lincoln Blvd., Tracy, CA 95376 <br />Phone # 510-657-8500 <br />Contact Roger Batra <br />A2. OWNER <br />Name Quik Stop Markets, Inc. <br />Address 4567 Enterprise Street, Fremont, CA 94538 <br />Phone # 510-657-8500 <br />Contact Debbie Markovich <br />A3. C U P A <br />Name San Joaquin County Environmental Health <br />Address 1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Notified July 25, 2017 <br />Inspector Cesar Ruvalcaba <br />Phone # 209-468-3442 <br />A4. TESTING CONTRACTOR <br />Name Walton Engineering, Inc. <br />Address P.O. Box 1025, W. Sacramento, CA 95691 <br />Lic # 617238 A, B, Haz <br />Contact Veronica Freitas <br />Phone # 916-373-1166 <br />I. LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: <br />Vaporless VMI LDT-890 <br />Tank number <br />1 <br />2 <br />3 <br />Product contained <br />87 Gasoline <br />89 Gasoline <br />91 Gasoline <br />Leak Detector Type <br />MLLD <br />MLLD <br />MLLD <br />Leak detector make/model <br />VMI 99LD-2000 <br />VMI 99LD-2000 <br />VMI 99LD-2000 <br />Serial number <br />illegible <br />illegible <br />illegible <br />Functional Element Holding (psi) <br />30 <br />31 <br />29 <br />Resiliency (ml) <br />55 <br />50 <br />50 <br />Test leak rate (gph) <br />3.00 <br />3.00 <br />3.00 <br />Pump pressure (psi) <br />30 <br />31 <br />29 <br />Metering pressure (psi) <br />22 <br />18 <br />17 <br />Pressure Restriction Reduction (psi) <br />8 <br />13 <br />12 <br />Length of Restriction Test (seconds) <br />30 <br />30 <br />30 <br />Full Flow Opening time (seconds) <br />3 <br />3 <br />3 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />Signature: <br />Technician: Scott Beall B45116 8319310 <br />WALTON <br />ENGINEEWNG, INC, <br />Date: August 9, 2017 <br />2DI 7 Willon Engineering, Inc, <br />