JUN-16-2010 09:09 Service Station Systems 408 938 8888 P.05 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By. [I Piping Manufacturer 0 Industry Standard Ij Professional Engineer <br /> Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum p Hydrostatic <br /> [3 Other(Specify) <br /> Test Equipment Used: Test reducer boots,Nitrogen and gauges Equipment Resolution:0.5%of span <br /> lig <br /> �N= Piping Run N 87 Piping Run;4 89 Piping Run N 91 Piping Run#Diesel <br /> Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Smith Smith Smith Smith <br /> Piping Diameter: Y 3" Y <br /> Length of Piping Run: 100, too, 100, loo, <br /> Product Stored: Gasoline Gasoline Gasoline Diesel <br /> Method and location of Reducer boots/fittings Reducer boots/fittings Reducer boots/fittings Reducer boots/fittings <br /> piping-run isolation. <br /> Wait time between applying <br /> pressure/vacuum/water and 10 minutes 10 minutes 10 minutes 10 minutes <br /> starting test: <br /> Test Start Time: 9:00 am 9-.00 am 9;00 am 9:00 am <br /> Initial Reading(Rj): 5 psi 5 psi 5 psi 5 psi <br /> Test End Time: 10:00 am 10:00 am 10:00 am 10:00 am <br /> Final Reading(RF): 5 psi 5 psi 5 psi 5 psi <br /> Test Duration: I hour I hour I hour I hour <br /> Change in Reading(11p-111): None None None None <br /> I Pass/Fail Threshold or No detectable loss No detectable loss No detectable loss No detectable loss <br /> I Criteria: I <br /> Test Result: 0 Pas 0 Fall Fmi Pass 0 Fail 0 Pass 0 Fail M Pan 0-Fail <br /> Comments—(include information on repairs made prior to lestin ,. and recommendedV.0 or ailed tests) <br />