Laserfiche WebLink
i <br />IBEX r-acisian Tank T sir <br />BROCKWAY S TANK TESTING Bakersfield, CA. USA x( 05) 834-1146 <br />Performed for: <br />Test Location: <br />Contel <br />430 West Center St. <br />Manteca, CA <br />Test Identification : cntlmn-1 <br />Test Date : 07-25-1995 <br />Start Data Collection : 14:48:42 <br />Ending Test Period : 16:50:09 <br />Time Filled for Test : + 4 hrs. top off only <br />TANK ID. <br />:Backup Gen <br />CONTENTS <br />:Diesel <br />Volume <br />:3060 <br />Diameter <br />:15 <br />Depth Bury <br />:13 <br />Product level <br />:83 <br />Groundwater <br />:> 15 FT <br />Pump Type <br />:Generator <br />Tank Type <br />:2 Wall <br />Water in Tank <br />:0 <br />Test Fluid <br />:Diesel <br />Vapor Recovery <br />:N/A <br />Average Rate of.Change is based on 238 Data Points <br />Standard Deviation ............. .0067 Gallons <br />- Volume change of Tank Contents - <br />Net Volume * ( 60 min/Test Time) <br />-.0161 Gal. * ( 60/ 61.34 min.) _ -.0157 Gph. <br />- Volume change due to Temperature -- <br />Avg. Temp. * Volume * Coef. of Expn. * (60 min./ Test Time) <br />0.0125 Deg.F * 3060 Gal. * 0.00043 * 60/ 61.34 = 0.0162 Gph. <br />Net change = Level Volume - Temperature Volum <br />NET CHANGE ... —.0399 GPH. <br />Based on the Information provided and the Data Collected <br />This Tank & Flooded Lines Test has...... PASSED <br />Certified Tester : Robert Brockman # 92-1251 , This Test complies with U.S.EPA and NFPA requirements. <br />No other warrantees are expressed or implied. <br />