Laserfiche WebLink
n <br />Name of ATGS Tidel Environmental Monitoring System <br />Version EMS 2000, EMS 3000 Series Models <br />Limitations on the Results <br />The performance estimates above are only valid when: <br />u <br />• The method has not been substantially changed. <br />• The vendor's instructions for installing and operating the ATGS are followed. _ <br />• The tank contains a product identified on the method description form. <br />• The tank is no larger than 15,000 gallons. <br />• The tank is at least 50 percent full. <br />• The waiting time after adding any substantial amount of product to the tank is 2 hours. <br />• The temperature of the added product does not differ more than 6.4 degrees <br />Fahrenheit from that already in the tank. <br />40 The total data collection time for the test is at least 6 hours. <br />Other limitations specified by the vendor or determined during testing: <br />none <br />ability> Safety disclaimer: This test procedure only addresses the issue of the ATG system's <br />detect leaks.does ♦ • - <br />nt for safety hazards. <br />resultsthat the presented •.:. form are those obtained during -. evaluation. <br />.•. .. •certify <br />that the evaluation was performed according to one of the following: <br />(X) standard EPA test procedure for ATGS <br />O alternative EPA test procedure for ATGS <br />H. Kendall Wilcox, Ph.D. Ken Wilcox Associates <br />(printed name) (organization performing evaluation) <br />Blue Springs, MO 6401 s <br />astate. • <br />February 14. .. 0.0 <br />(date) (phone number) I <br />ATGS Evaluation Page 2 of 2 <br />