SWRCB, January 2002 <br />Page 6 of 7 <br />Epi! t11 1:� iy K11el rI Iglu i Diel Iyil l <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer N Industry Standard ❑ Professional Engineer <br />❑ Other (Specift) <br />Test Method Uses: ❑ Pressure ❑ Vacuum 19 Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon TS -STS Sump Testing S stem E ui me nt Resolution: 0.001 <br />Fill Sum #1 Fill Sum # Fill SUME # Fill Sume # <br />Sump Diameter: 36" <br />Sump De the <br />45" <br />Height from Tank Top to Top of <br />Hi hest Pi in Penetration: <br />16" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />1711 <br />Condition of sump prior to <br />testing: <br />Good <br />Portion of Sump Tested <br />26" <br />Sump Material: <br />Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and <br />30 min. <br />starting test: <br />Test Start Time: <br />9:15 am <br />Initial Reading (RD: <br />7.1493" <br />Test End Time: <br />9:30 am <br />Final Reading (RF): <br />7.1491" <br />Test Duration: <br />2 x 15 min. each test <br />Chane in Reading (RF -R : <br />-0.0002" <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />9 +�'� � - /r 11 J �� <br />d Mf � r �,� �' sem'! i �� 1�G1'� � �� � � �tF{ �l'��. `K�' 3��57 ��r`j/�✓1�%"r'L� � �m �� �i���i�' ��!/ P ,v <br />Is there a sensor in the sump? <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />Yes <br />detected? <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Revision: <br />