Laserfiche WebLink
SWRCB, January 2002 <br />Page 7 of 7 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer <br />❑ Other (Specify) <br />N Industry Standard ❑ Professional Engineer <br />Test Method Uses: <br />❑ Pressure <br />❑ Other (Specify) <br />❑ Vacuum N Hydrostatic <br />Test Equipment Used: Incon TS -STS Sump Testing S stem <br />Spill Box # 1 Spill Box # <br />er: 12" <br />7Waittime <br />Equipment Resolution: 0.001 <br />Spill Box # Spill Box # <br />l0"tween <br />applying <br />pressure/vacuum/water and <br />starting test: <br />30 min. <br />Test Start Time: <br />10:11 AM <br />Initial Reading (RI): <br />0.3729" <br />Test End Time: <br />10:26 AM <br />Final Reading (RF): <br />0.3729" <br />Test Duration: <br />2 x @ 15 min. each test <br />Change in Reading (RF-RO: <br />0 <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />IN <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />No Repairs Made. <br />Please direct any comments regarding this form to: <br />SWRCB UST Program, Attn: Scott Bacon <br />1001 "I" Street, Box 944212 <br />Sacramento, CA 95814 <br />Phone: (916) 341-5873, Fax: (916) 341-5808 <br />e-mail: bacons@cwp.swrcb.ca.gov <br />Revision: <br />