SPECIFICATION FOR UL -142 DOUBLE -WAIL SECONDARY CONTANMENT <br />CONSTRUCTION DAY TANK WITH ON -BOARD SUPPLY DUPLEX PUMPS <br />DRAWING FROM A REMOTE MAIN SOURCE TANK AND ON -BOARD <br />DUPLEX RETURN PUMPS RETURNING OVERFLOW TO A REMOTE MAN <br />SOURCE TANK, <br />THE FOLLOWING DEFINES A DAY TANK WITH A DUPLEX PUMP SYSTEM <br />OSIGNED FOR ORNERY OF FUEL FROM A SOURCE STORAGE TANK TO <br />A DAY TANK, APPROXIMATELY 200-11EE1 HORIZONTAL AND WITHIN <br />18 -FEET OF VERTICAL LIFT FROM THE LOWEST POINT VM A PUMP SET <br />INSTALLED ON THE DAY TANK, AT THIS SITE, CONSIDERATION MUST BE <br />GIVEN TO SUCTION LIFT CHARACTERISTICS OF PUMPS: THIS SYSTEM <br />WILL OPERATE IN THE SUCTION LIFT CAPABILITY CURVE OF THE <br />PUMPS. THEREFORE. PIPE SIZE OF BOTH SUPPLY AND RETURN LINES <br />ISPARAMOUNT TO BOTH REDUCE FRICTION IN ME SUPPLY UNE AND <br />ALLOW FOR FREE ROW RETURN O NEL IN THE RETURN UNE. A <br />FOO I VALVE IS REQUIRED IN THIS SYSTEM IF SOURCE TANK 6 BELOW <br />DAY TANK. IF SOURCE TANK IS BELOW DAY TANK, MANUAL PRIMING IS <br />REQUIRED. ONCE PRIMED, ME SYSTEM REMAINS SO FROM THE <br />FOQT-VALVE ON THE SUPPLY LINE IN THE MAIN SOURCE TANK TO <br />THE INLET OFTHE DAY TANK MOUNTED SUPPLY PUMPS. <br />ANLL FLOW OVERFLOW RE111RN PIPE FROM EACH DAY TANK BACK <br />TO THE BULK SOURCE TANK MUST BE PROVIDED. WORKING VENTS TO <br />OUTDOORS MUST BE PROVIDED AS WELL AS AN EMERGENCY VENT FOR <br />TANKS 100 GALLONS AND LARGER. <br />FUEL OIL DAY TANK (275 CAL). <br />1.0 GENERAL: PROVIDE A PACKAGED DESIGN FUEL OIL DAY TANK <br />FOR EACH PRIME MOVER. DAY TANK SHALL BE COMPLETE IN <br />ALL RESPECTS N ORDER TO PROVIDE THE PRIME MOVER WITH <br />A RELIABLE, LOCAL SOURCE OF FUEL. DAY TANK SHALL BE FOR <br />USE WHH MAIN TANK AND FUEL DELIVERY SYSTEM DESCRIBED <br />ABOVE IN ORDER TO PROVIDE AN AUTOMATIC, SELF-REFCLNG <br />NEL SUPPLY SYSTEM, <br />1.1 ME DAY TANK SHALL BE DESIGNED AND SUPPLIED AS AN <br />ENGINEERED SYSTEM BY ME MANUFACTURER. EACH TANK SHALL <br />BE OF PACKAGED DESIGN TO INCLUDE ALL INLET FLOW <br />CONTROL DEVICES, OTHER VALVES, LEVEL CONTROLS, PUMP <br />CONTROL, INDICATORS, ALARMS AND ALL OTHER DEVICES AS <br />REQUIRED TO FORM AN INTEGRATED, FLCTKNAL SYSTEM SUCH <br />THAT FIELD INSTALLATION IS RESTRICTED LARGELY 10 EXTERNAL <br />PIPING, WIRING AND SUCH INTERMEDIATE DEVICES THAT ARE <br />REQUIRED BY CODE AND/OR GOOD ENGINEERING PRACTICE TO <br />INTERCONNECT THE BULK SOURCE OF SUPPLY TG THE DAY <br />TANK, THE DAY TANK TO THE PRIME MOVER AND TO PROVIDE <br />FOR EXTERNAL VENTS AS PER LOCAL CODES AND UL142, <br />NFPA31 AND NFPA3I. <br />1.1 .1 ME SYSTEM SHALL BE FOR USE WITH FUEL OI AS DESCRIBED <br />BY NFPA321, 'BASIC CLASSIFICATION OF FLAMMABLE AND <br />COMBUSTIBLE UQUIDS'. AS DEFINED BY THIS STANDARD, THE <br />FUEL SUPPLY SYSTEM SHALL BE FOR USE WITH TOMBURIBLE <br />LIQUIDS', THOSC HAVING A FLASH POINT AT OR ABOVE IDO'F <br />AND M HER DEFINED AS CUSS II OR CLASS III LIQUIDS. N <br />NO CASE SHALL A LIQUID DEFINED AS 'FLAMMABLE. OR AS <br />TLA55 T OR AS HAVING A FLASH POINT LESS THAN IDO'F BE <br />USED. IN EVERY CASE, THE SYSTEM SHALL NOT BE USED OR <br />APPLIED AT A TEMPERATURE IN EXCESS OF THE MSH POINT <br />OF THE CONTENTS. ELECTRICAL EQUIPMENT USED N THE <br />SYSTEM SHALL BE IN ACCORDANCE WITH NFPA30. SECTION 5-7. <br />WHEREIN IT STATES 'FOR AREAS WHERE CLASS II OR CLASS IF <br />LIQUIDS ONLY ARE STORED OR HANDLED AT A TEMPERATURE <br />BELOW HEIR FLASH POINTS, THE ELECTRICAL EQUIPMENT MAY <br />BE INSTALLED IN ACCORDANCE WITH PROVISIONS OF NFPA70, <br />NATIONAL ELECTRIC CODE FOR ORDINARY LOCATIONS..: <br />1.11 THE SYSTEM SHALL BE DESIGNED AND INSTALLED IN <br />ACCORDANCE WITH APPUCABLE SECTIONS OF NFPA30 NFPAST <br />NFPA37, 'UL80 AND ULI42. THE DAY TANK SHALL BEAN ME <br />LABEL OF UNDERWRITERS LABORATORIES STANDARD 142 AND <br />UL508. <br />1.2 INSIALU110N GENERAL. THE DAY TANK SHALL BE INSTALLED <br />ADJACENT TO THE PRIME MOVER, CN THE SAME GRADE. INSTALL <br />(AS SHOWN ON THE PLAN DRAWINGS, [AS DETAILED HEREIN]) <br />ON A NOUSEKEEPING PAD ADJACENT TO THE PRIME MOVER. <br />ANCHOR TANK 70 ME PAD. <br />1.2.3 PROVIDE SCHEDULE 40, ASTM A 53. BLACK IRON PIPE <br />CONNECTIONS TO THE DAY TANK AS SHOWN, MAKE ALL <br />CONNECTIONS TO FIXED INSTALLED PIPE WITH PIPE UNIONS TO <br />FACILITATE TANK SERVICE/REMOVAL. <br />(1) SUPPLY TO DAY TANK, INLET TO DAY TANK PUMP <br />(2) DAY TANK DUPLEX RETURN PUMPS SET TO RETURN <br />OVERFLOW TO BULK SUPPLY <br />(3) SUPPLY AND RETURN TO PRIME MOVER. AS RECOMMENDED <br />BY MANUFACTURER <br />(4) VENT SIZES SHALL BE AS SHOWN AND AS REQUIRED BY <br />LOCAL CODES AND BY UL 142,NFPA31 AND NFPA37 AS <br />WELL AS PROJECT SPECIFICATION REQUIREMENTS. <br />1.3 DAY TANK RATINGS <br />13.1 CAPALIIY. (275) CA LONS <br />1.31 POWER REQUIREMENTS: (110)V AC, SINGLE-PHASE, 60HERTZ. <br />15A DEDICATED BRANCH CIRCUIT <br />1 3 DAY TANK CONSTR 7TON <br />1.3.3.1 ALL WELDED STEEL ATMOSPHERIC TANK OF RECTANGULAR, <br />DOUBLE-WALL SECONDARY CONTAINMENT. WELDS] <br />CONSTRUCTION BUILT N ACCORDANCE DOTH CODES AND <br />STANINDO <br />DARDS N07D ABOVE FOR OR USE NTH FUEL OIL. <br />1.332 PIPE THREAD CONNECTIONS SHALL BE PROVIDED FOR FUEL <br />OIL SUPPLY FROM REMOTE PUMP SET, SUPPLY TO PRIME <br />MOVER, RETURN FROM PRIME MOVER, OVERFLOW TO MAN <br />TANK, VENTS, AND DRAIN WITH FIRE RATED BALL VALVE. A <br />WEATHERPRDOF. SCREENED VENT CAP SHALL BE PROVIDED <br />AS A LOOSE ITEM FOR FIELD INSTALLATION AT ME OUTDOOR <br />VENT TERMINATION. A WEIGHTED TYPE EMERGENCY VENT CAP <br />SHALL BE SUPPLIED INSTALLED ON THE PRIMARY TANK AND <br />DAY TANK SPECIFICATION <br />SECONDARY CONTAINMENT EMERGENCY VENT PORTS (IN <br />GALLON AND LARGER), <br />1,133 THE TANK SHALL BE EQUIPPED WITH A WELDED STEEL <br />CHANNEL BASE SUITABLE FOR BOLT ATTACHMENT TO A <br />CONCRETE PAD <br />1.3.3,4 THE TANK SHALL HAVE INTERIOR CORROSION INHIBITOR TO <br />DETER CORROSION PRIOR TO INSTALLATION AND USE <br />1.3.15 THE EXTERIOR OF THE DAY TANK SHALL RECEIVE A <br />HEAVY-DUTY INDUSTRIAL ANN -CORROSION COATING AND BE <br />FINISH PANTED <br />1.13B ALL DAY TANK SYSTEM COMPONENTS SHALL BE PROTECTED <br />BY A REMOVABLE OR HINGED STEEL EQUIPMENT COVER, <br />1.3.3.7 DAY TANK SHALL BE FACTORY LEAK TESTED AT 3PSI. <br />1AAA THE TANK SHALL BE STEEL DOUBLE-WALL SECONDARY <br />CONTAINMENT CONSTRUCTION BEARING THE M 142 LABEL, <br />THE CONTAINMENT SHALL BE EQUIPPED WITH A LEAN <br />DETECTOR THAT SHALL ACTIVATE THE TEAM ALARM <br />DESCRIBED BELOW. A OWN WITH FIRE RATED RAL VALVE IS <br />TO BE SUPPLIED. THE CONTAINMENT SHALL BE EQUIPPED <br />WITH A SEPARATE EVENT AS REQUIRED BY UL 142, <br />1.33 9 SUPPLY FIRE RATED BALL VALVES AS FOLLOWS. <br />1. DAY TANK DRAM <br />2. SECONDARY CONTAINMENT DI <br />1A FUEL DELIVERY SYSTEM: PROVIDE INSTALLED UPON THE DAY <br />TANK. A DUPLEX FUEL OIL SUPPLY PUMP A DUPLEX FUEL <br />al RETURN SET AND DUPLEX PUMP CONTROLLER WITH <br />AUTOMATIC ALTERNATOR FOR SUPPLY OF FUEL FROM THE <br />MAIN TANK TO THE DAY TANK AND RETURN FROM OVERFLOW <br />TO THE MAN TANK. THE FILL 6 A SUCTION -CPT <br />APPLICATION: ADEQUATE PIPE SIZES MUST BE USED IN THE <br />SYSTEM AND A FOOT VALVE MUST BE INSTALLED IN THE <br />EXISTING MAIN TANK IF MAIN IS BELOW LEVEL OF DAY TANK. <br />MANUAL PRIMING OF THE SYSTEM IS REQUIRED. <br />1 A DUPLEX PULPS: 2 GPM SUPPLY PUMPS AND4 GPM <br />RETURN PUMPS AT X725 RPM AT 1]25 RPM. WHEN <br />OPERATING VNTH NEL OIL HAVING A VISCOSITY OF 32SSU <br />1.42 DIRECT DRIVE, MOTOR DRIVEN PUMPS COUPLED VIA <br />FLEXIBLE COUPLING. <br />1.4.3 MOTORS TO BE TEFC CONSTRUCTION, HP AS REQUIRED <br />FOR PUMP AT ISD PSI NEMA TYPE B, CONTINUOUS DUTY AT <br />WC. 1725 RPM. 120V AC. 60 HERR, 1.15 SERVICE <br />FACTOR <br />IAA PUNAS TO BE DIRECTLY DRNEN, POSITIVE DISPLACEMENT, <br />INTERNAL GEAR TYPE WITH MECHANICAL SH4FT SEA AND <br />CAST IRON BODY, MACHINED STEEL GEARS. <br />145 FIRE RATED SHUTOFF BALE VALVES ON PUMP INLETS <br />4.6 PUMP CHECK VALVE, SPRING -TYPE, CAST IRON <br />CONSTRUCTION <br />-1 1 FLOWSWTCH EACH PUMP <br />1,48 SUCTION STRAINER, CAST NON WE TYPE NEL OIL <br />STRWHER ON EACH PUMP RVION <br />149 PROVIDE A PISTON TYPE, 0.1 GALLON PER STROKE HAND <br />PUMP INSTALLED AND PIPED AND EQUIPPED WITH <br />FIRE -PARD SHUTOFF VALVES. <br />1.5 DAY TANK LEVEL CONTROLLER, AUL LISTED. INTEGRATED <br />DESIGN. DIGITAL LEVEL CONTROLLER SHALL BE SUPPLIED <br />WHICH PROVIDES DIFFERENTIA LEVEL CONTROL FOR <br />ACTNATION O PUMPS. DUPLEX PUMP ALTERNATOR, TANK <br />LEVEL INDICATION, SYSTEM ALARMS AND MANUAL OPERATING <br />CONTROLS. LEVEL CONTROLLER SHALL BE SEL -CONTAINED <br />AS A UNIT WIRMN A NEMA4 ENCLOSURE INTEGRAL WITH THE <br />DAY TANK ASSEMBLY. <br />1.5.1 PLC BASED WITH 6 -MCH, COLOR, TOUCH -PANEL <br />OPERATOR INTERFACE <br />1.52 DML LEVEL SENSOR INPUT. <br />-4-20W CONTINUOUS SENSOR, ANALOG -TO -DIGITAL INPUT <br />-POINT SENSING FLOAT SWITCHES: LOW, REFILL START, <br />WALL STD', HIGH, CHECKPOINT FOR AUTOMATIC CROSS <br />CHECK O SENSORS <br />153 LEAN( SENSOR <br />1.54 SPARE I/O FOR OPTIONS AND DESIGN -BUILD FEATURES <br />1.55 .008115 AND ETHERNET NETWORK COMPATIBLE <br />3.5.6 4-20MA LOOP OUTPUT FOR TANK LEVEL <br />1.57 OPERATOR TOUCH -PANEL INTERFACE FUNCTIONS: <br />AOA SWITCH <br />-TEST <br />-RESET <br />-ALARM SILENCE <br />-NUMERIC DISPLAY Or TANK LEVEL IN GALLONS (LITERS) <br />-GRAPHIC CONDITION DISPLAY O TANK LEVEL AND <br />PUMP/STATUS/HARM CONDITION <br />-MESSAGE INDICATORS FOR STATUS AND ALARM, INCLUDING: <br />-NORMAL OPERATION <br />-PUMP RUNNING (EL'L, RETURN, SINGLE OR MULTIPLE PUMPS) <br />TANK FILING <br />-LOSS OF FLO. <br />-LOT <br />-CRUICAL LOW <br />-MGN <br />-CRITICAL HIGH <br />_LOOK <br />-NOT IN AUTO <br />-CONTROLLER FAILURE WITH SPECIFIC MESSAGE <br />1.5.8 RELAY CRY CONTACT OUTPUTS FOR THE FOLLOWING <br />(5A,SPDT)'. <br />LOW ALARMS <br />HIGH ALARMS <br />LEAK <br />NOT IN AUTO <br />1.6 DAY TANK TESTING <br />1.6.1 THE BAY TANK SHALL BE SUPPLIED WITH MANUFACTURERS <br />TEST CERTIFICATES AS BELOW TANK TESTS'. PRESSURE TEST, <br />LEAK PROOF TEST AND STRUCTURAL INTEGRITY/ A PERANCE <br />TEST. <br />1.6.11 LEVEL CONTROLLER: OPERATIONAL TEST O LEVEL SENSORS. <br />LEVEL INDICATOR LEVEL CONTROL, AWN, BACKUP DEVICES. <br />1.6.1.3 PUMP: VACUUM TEST. FLOW TEST. PRESSURE TEST, LEAK <br />PROOF TESTAMPERE/VOLTAGE TEST, LOAD TEST, OVERLOAD <br />TEST. <br />17 DAY TANK MANUAL. <br />L7 THE DAY TANK SHALL BE SUPPLIED WITH AN ILLUSTRATED <br />MANUFACTURER'S MANUAL THAT INCLUDES ME FOLLOWING: <br />1.7.1.1 REGISTRATION CERTIFICATE. <br />17.1.2 GLOSSARY. <br />1.7.1.3 EQUIPMENT LIST. <br />1 ] 1 4 DETAILED DESCRIPTION OF OPERATION, <br />17.1.5 PUMP SPEOPWION, <br />17.1.6 NSTAI(A INSTRUCTIONS. <br />17.17 TROUBLE SHOOTING INSTRUCTIONS. <br />1 7.1 8 MAINTENANCE INSTRUCTIONS. <br />133 9 PIPING DIAGRAM. <br />17.1.10 ELECTRICAL DRAWING <br />X.].1.11 DIMENSIONAL DRAWING. <br />1.].1.12 WARRANTY CARO. <br />FUEL OIL GENERAL NOTES <br />1. THE LOCATIONS SHOWN OF ME EXISING DIESEL FUEL OIL LINES <br />ARE APPROXIMATE AND ARE TO IDENTIFY POINTS OF CONNECTIONS <br />FOR NEW PRODUCT LINES OR FOR COORDINATION OF CLEARANCES <br />BETWEEN EXISTING AND NEW PIPING, INDICATION OF EXISTING <br />P"NO SHALL NOT BE CONSIDERED AS AN EXACT LOCATION OR A <br />COMPLETE SURVEY OF EXISTING INSTALLATION, <br />2. THESE DRAWINGS ARE DIAGRAMMATIC. THE CONTRACTOR SHALL <br />ASSUME FULL RESPONSIBILITY OF COORDINATION WITH VARIOUS <br />TRADES AND INCLUDE TURNS, BENDS, ADDITIONAL LENGTHS OF <br />PIPING AND ELEVATION CHANGES. AND TRANSITIONS WITHOUT <br />ADDITIONAL COST TO THE OWNER, <br />3. LOCATION AND ELEVATION OF EXISTING UNITIES SHAT BE <br />CONSIDERED AS APPROXIMATE AND INCOMPLETE. BEFORE ANY WORK <br />IS STARTED, VERIFY AND COORDINATE ELEVATIONS AND SIZES OF <br />EXISTING PIPING. DISCREPANCIES BETWEEN FELD DATA AND DATA 01 <br />PUNS AND SPECIFICATIONS SHALL BE REPORTED TO ME <br />ARCHITECT, DO NOT PROCEED WIN INSTAULIDDN IN AREAS OF <br />DISCREPANCIES UNTIL DISCREPANCIES HAVE BEEN RESOLVED. <br />4. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE <br />FINISHED WORK. THEY DO NOT INDICATE THE METHOD OF <br />CONSTRUCTION. SUPERVISE AND DIRECT THE WORK FOR AL <br />CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND <br />PROCEDURES <br />5. VALVES SHALL BE LINE SIZE UNLESS OTHERWISE NOTED. <br />6. NO HOLES SHALL BE DRILLED CR CUT IN OR THROUGH ANY <br />STRUCTURAL ELEMENT WITHOUT APPROVAL OF ME ARCHITECT <br />OR STRUCTURAL ENGINEER. <br />7. AS AMINIMUM STANDARD, ALL WORK SHALL COMPLY WITH THE <br />2013 REQUIREMENTS OF ME CALIFORNIA PLUMBIC CODE, AND <br />CALIFORNIA CODE OF REGULATIONS TIRE 24. <br />g. FIELD OBSERVATION AND SUPPORT SERVICES PERFORMED BY THE <br />ENGINEER PRIOR T0, DURING, OR AFTER CONSTRUCTION, ARE <br />PERFORMED FOR THE PURPOSE OF ACHIEVING QUALITY CONTROL <br />AND SHALL NOT BE CONSTRUED AS SUPERVISION OF <br />CONSTRUCTION. <br />9. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED TEMPORA <br />AND PERMANENT PERMITS, INCLUDING LICENSES, CERTIFICATES, <br />PRECiGNS AND TESTS. <br />10 VERIFY ELECTRICAL CHARACTERISTICS WITH ELECTRICAL DRAWINGS <br />PRIOR TO 80 AND MATERIAL PURCHASE. <br />NOTICE TO CONTRACTOR <br />I. THE CONTRACTOR IS MADE AWARE OF THE DEDUCTIVE ALTERNATE <br />�I FOR THE USE OF BLACK STEEL PIPE FOR THE ABOVE THE <br />GROUND FUEL OIL PIPING, <br />2. ATTENTION IS BROUGHT TO THE CONTRACTOR FOR VERIFICATION OF <br />THE EXISTING NEL OIL POLISHING LINES. VERIFICATION IS <br />REQUIRED FOR THE FUEL OIL POLISHING LINES TO BE A DIRECT <br />CONNECTION TO THE UNDERGROUND NEL OIL TANK AND THAT NO <br />LINES ARE CONNECTED FROM THE FULL OL POLISHING STATION TO <br />THE EXISTING DAY TANK THRU ME EXISTING TRENCH. SHOULD THE <br />ENDINGS INDICATE THE UTTER, THE CONTRACTOR SHALL NOTIFY <br />INE OWNER AND THE ARCHITECT AS TO HON' TO PROCEED. <br />3. CONTRACTOR SHN.L VERIY THAT ME EXISTING NEL OIL POISHIN( <br />LINES FROM THE EXISTING POLISHING STATION TO THE <br />UNDERGROUND TANK PRE IN GOOD WORKING CONOITION. PROVIDE X <br />TEN BABY PORTABLE POLISHING SYSTEM FOR ME EXISTING DIESE <br />FUEL IN UNDERGROUND TANK AND PROCEED TO A ONE TIME <br />POUSHING OF THE EXISTING NEL IN TANK, ONCE THE PROCEDURE <br />HAS BEEN DONE THE CONTRACTOR SHALL THOROUGHLY CLEAN TME <br />LINES AND PROCEED TO REMOVAL OF THE SYSTEM ABOVE AND <br />BROW GROUND IN A MANNER ACCEPTABLE TO ME AUITHORHIM <br />HAVING JURISDICTION. THE REMOVAL OF THE LINES IN THE <br />UNDERGROUND TANK SINP(S) SHALL BE EXECUTED MAINTAINING <br />THE INTEGRITY OF THE SUMP WALLS AND ANY OF ITS LEA( <br />DETECTION AND MONITORING SYSTEM. MANHOLE PIPE PENETRATIONS <br />SHALL BE SEALED PER THE SUMP MANUFACTURER'S <br />WCOMMENDKIMS. <br />A CONTRACTOR SHALL VMLY THAT ME EXISTING NEL OIL <br />UNDERGROUND TANK REMANING SYSTEMS ARE IN GOOD WORKING <br />CONDITION AND ANY OEMMENTK FACTORS SHALL BE REPORTED <br />TO THE DINER AND ME ARCHITECT PRIOR TO FOLLOWING WITH <br />PROCEDJRE. <br />AFF <br />AEG <br />FUEL OIL LEGEND <br />SYMBOL <br />ABBREV. <br />IDENTIFICATION <br />-(E)XX-OR -I <br />(E)XX <br />EXISTING PIPING OR ECUPMED TO REIMN <br />NN(E)XX-OR <br />(E)XX <br />EXISTING RPM OR EWPWNWF TO BE MAXISHEO <br />-DRQ <br />(E)EXISTING <br />EXIST. <br />NEW PPC& OR EGIPMEN7 <br />-FOS- <br />FOS <br />FURL SUPPLY PIPING <br />-FOR- <br />FOR <br />FUEL RETURN PIPING <br />-FOV - <br />FOV <br />FUEL OIL VENT PIPING <br />J <br />GAL. <br />RISER DOWN <br />---------- 0 <br />PODUs <br />RIBNIEM DITECION I INVENTORY MONITORING SST <br />RISER UP <br />�- <br />MIN. <br />ROW IN DIRECTION OF ARROW <br />N <br />OPERATING WEGHT <br />POUND PER SQUARE INCH <br />CATE VALVE <br />PC NO PER SQUARE FOOT <br />R <br />T OF <br />BNL VALVE <br />pi <br />W <br />TYPICAL <br />MOTORIZED VALVE <br />-�-- <br />REDUCER OR INCREASER <br />-�- <br />PUMP <br />.._.-._..�..-__ <br />NTT RISE TO ABOVE PARAPET <br />_ <br />FULL 0C COURANT ON FIXTURE SYMBOL <br />FLEXIBLE CONNECTION <br />® <br />FOC <br />PONT OF CO@ECTION <br />(ilio <br />POD <br />PONT OF DISCONNECTION <br />AFF <br />AEG <br />ABOVE FN6HEp FLOOR <br />ABOVE FINISHED GROUND <br />ARCH_ <br />BEL. <br />ARCHITECTURAL <br />BELOW <br />8,0 P. <br />BOTTOM OF PIPE <br />DIA <br />ON. <br />DAVEY R <br />DOWN <br />DWG/DWGS. <br />DRAWING/DRAWINGS <br />EA <br />EACH <br />(E)EXISTING <br />EXIST. <br />EXISTING <br />ELECT. <br />FAS <br />ELECTRICAL <br />NEL AIR SEPARATOR <br />REX. <br />FLEIOBLE <br />`PDP <br />FUEL PIPE DROP PR <br />FR <br />FTFEE <br />FROM <br />FTP <br />FUEL TRANSFER PUMP <br />GAL. <br />C-ALLON, <br />LBS <br />LDN <br />PODUs <br />RIBNIEM DITECION I INVENTORY MONITORING SST <br />MAX. <br />MFGR. <br />MP%WUM <br />MANUFACTURER <br />MIN. <br />MINIMUM <br />ORW,. <br />PSI <br />OPERATING WEGHT <br />POUND PER SQUARE INCH <br />PSF <br />PC NO PER SQUARE FOOT <br />R <br />T OF <br />SQUARE FEE) <br />TOP OF PIPE <br />TVP. <br />TYPICAL <br />MEL O& DETAIL NUMBER <br />FML GL OEM SYMBOL <br />NEI M DRAWMG NIpXDR WHERE DTA& 6 SIWMN <br />Da OIL EOUFWW OR FIXTURE ABBREVIATION <br />XX <br />FULL 0C COURANT ON FIXTURE SYMBOL <br />FUEL 01. EQUIPMENT OR FIXTURE DESIGNATED WAM%R <br />WARNI <br />PRIOR TO COMMENCING EXCAVATION CONTRACTOR <br />SHALL COORDINATE WITH THE OWNER AND RECORD <br />DRAWINGS THAT MAY INDICATE EXISTING UTILITIES IN <br />THE AREA AFFECTED BY THIS PROJECT. <br />F AHLA • X:.AL-i <br />a ettoro eeacwer <br />