Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑UDC Manufacturer C!Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> 728" <br /> DC#1&2 UDC#3&4 UDC#5&6 UDC#7&8 <br /> UDC Manufacturer: tal Containment Total Containment Total Containment Total Containment <br /> UDC Material: ly Plastic Poly Plastic Poly Plastic Poly Plastic <br /> UDC Depth: 31" 32" 35" <br /> Height from UDC Bottom to Top 12" 15" 14" 14" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 7" 10" 7" 8" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested' Water Line 17" Water Line 18" Water Level 16" Water Level 16" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both Yes Yes Yes Yes <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail- Yes Yes Yes Yes <br /> safe shutdown?* <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 9:00 9:05 9:40 9:45 <br /> Initial Reading RI): .001 .001 .001 .001 <br /> Test End Time: 9:30 9:35 10:10 10:15 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-RI): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass Pass <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced and <br /> verified functional after testing? <br /> Yes Yes Yes Yes <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 3 a <br /> 0 2017 <br /> r.wwRQNMENTAL HEALTH <br /> FTENT <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to anv of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />