Laserfiche WebLink
Quik Stop Markets, Inc. <br /> 4567 Enterprise Street•Fremont,CA 94538•(510)657-8500•Fax: (510)657-1544 <br /> C— <br /> t <br /> June 4, 2004 <br /> VIA CERTIFIED MAIL - <br /> .. <br /> a <br /> �r <br /> Steven C. Shih, Sr. R.E.H.S. <br /> San Joaquin County <br /> Environmental Health Department <br /> 304 East Weber Avenue, 3rd Floor <br /> Stockton, CA 95202 <br /> Re: UST Inspection <br /> Quik Stop Market#121 <br /> 1196 West Louise Avenue, Manteca <br /> Dear Mr. Shih: <br /> As requested in your inspection report(copy enclosed)dated 5/6/04,the following <br /> documents/comments are provided: <br /> 1. Certificate of Insurance for USTs(mechanism to demonstrate financial <br /> responsibility)has been renewed,however,to date I have not received my <br /> copy. When received, the Certification of Financial Responsibility will be <br /> provided to all Agencies for all Quik Stop tanks. <br /> 2. Line, LD, Monitor Certification Test Results will be mailed directly from <br /> Triangle Environmental, Inc. (testing conducted on 5/6/04, in your <br /> presence. <br /> 3. Monitoring and Response Plans in San Joaquin County required format <br /> (copies enclosed)have been added to the Quik Stop standard plans. <br /> 4. The mechanical leak detector on the 87 Octane tank was replaced under <br /> permit on 5/17 by Elite IV Contractors. Ray von Flue was in attendance. <br /> 5. No maintenance or repair record that correlates with a sensor out alarm on <br /> the premium annular probe on 4/26/04 was noted. Possibly a spurious <br /> signal that did not repeat. Maintenance and repair records are attached. <br />