Laserfiche WebLink
c w <br /> PILL CONTAINER CONTAINMENTTESTING <br /> Test Method By: Manufacturer • Industry d <_ Professional Engr. Other(see ) <br /> Test Method Uses: Pressure Vacuum • Hydro (see ) <br /> Measuring Equipment Used: Level Change Indicator (Caldwell system 20011 Walton 'ng) <br /> Description Tank#1 Tank#2 <br /> Spill container manufacturer OPW OPW <br /> Spill container capacity (US gallons) 5 Gallons 5 Gallons <br /> Spill container depth (inches) 12.25 13.25 <br /> Product contained Gasoline-87 Gasoline-91 <br /> Is Spill container bated in a sump? Yes Yes <br /> Does sump have a liquid sensor instar? No No <br /> Distance between fill adapter and 16" 16, <br /> vae2r adapter centers incus <br /> Condition of spill container prior to testing Dry Entire <br /> Portion of spill container tested Entire Dry <br /> Wait time for water level to stabilize (hr:min) 0:04 0:03 <br /> Depth of water level from bottom (inches) 12.00 13.00 <br /> Test start time 2:15 PM 2:20 PM <br /> Test end time 2:45 PM 2:50 PM <br /> Test duration (hr:min) 0:30 0:30 <br /> Change in water level (±0.000 inches) 0.000 0.000 <br /> Pass/Fail threshold (0.005 inches/h Hr.) 0.005 0.005 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> © 2003 Watton Engineering,Inc. <br />