Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00121 <br /> Tank#: 2 Work#: 20000898 <br /> Product: Unleaded Premium Test Date: 5/12/03 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX-2 <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): 72 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: Pump Brand: Red Jacket <br /> Test Rate(gph): System Type: Pressure <br /> Test Result: N/A Line Pressure(psi): 50 <br /> Line Start Time: 2:00 PM <br /> i <br /> Test Method: ULLAGE I Line End Time: 2:15 PM <br /> U11ageVolume(gals.): Line Start Level: 260 <br /> Ullage Test Time: Line End Level: 250 <br /> Ullage Vacuum(psi): i j Line Test Rate(gph): -0.011 <br /> Ullage Result: N/A Line Test Result: PASS <br /> COMMENTS <br />