Laserfiche WebLink
Triangle Environmental Inc <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00121 <br /> Tank#: 1 Work#: 7405332 <br /> Product: Unleaded Premium Test Date: 5/24/01 <br /> EMENEE01=1 <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 12000 Manufacturer: Red Jacket <br /> Diameter(in): 96 L/D Model: FX <br /> Product Level(in): L/D Serial#: 105988553 <br /> Liquid Volume(Gals): Line Drain Back(ml): 120 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.007 Holding Pressure(psi): 29 <br /> Coef. of Expansion: 0.000680 Metering Pressure(psi): 8 <br /> Water On Tank(in): 96 L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: 1:00 PM <br /> Test Method: TEI LT-3 <br /> Test End Time: 1:01 PM <br /> Pump Brand: Red Jacket <br /> Test Rate(gph): <br /> System Type: Pressure <br /> Test Result: PASS <br /> Line Pressure(psi): 50 <br /> 1 111 1 11 11 Line Start Time: 11:01 AM <br /> Test Method: ULLAGE Line End Time: 11:16 AM <br /> UllageVolume(gals.): Line Start Level: 210 <br /> Ullage Test Time: 1:00 PM <br /> Line End Level: 195 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): 0.002 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 2 <br />