Laserfiche WebLink
stapdard Models i <br />FORM NO. DESCRIPTION <br />794390-205 Piping Sump Sensor <br />Piping Sump Sensor Console Compatibility <br />The Series 7943 Piping Sump Sensor is compatible with the following consoles: <br />TLS -350° i ILS -350" TLS -2501 I TLS -250i Plus! ILS -250 <br />Series 8470 Series 8450 Series 7941 Series 7941 Series 7942 <br />'NOTE. An Interstitial Sensor Interface Module is required for use of the piping sump sensor with the TLS -350 system. <br />"NOTE.- A Two -Wire Module is required for use of the piping sump sensor with the ILS -350 system. <br />Standard Specifications <br />Power Requirements: Intrinsically safe power <br />supplied by Veeder-Root <br />TLS -350, ILS -350, <br />TLS -250i or ILS -250 <br />System <br />Sensor: <br />Type: <br />Contact Rating: <br />Switch Travel: <br />Temperature Rating: <br />Storage: <br />Operating: <br />Housing Material: <br />Hermetically sealed <br />magnetic reed <br />15 Watts <br />7/s inch to contact <br />-40°C to + 74°C <br />-0°C to + 60°C <br />PVC Schedule 40 Tubing <br />TYPICAL BRACKET MOUNTING <br />LEADER CABLE <br />CORD GRIP <br />MOUNTING BRACKET _ \. I <br />JUNCTION BOX <br />I 1 <br />II <br />MOUNTING SLEEVE <br />SUMP SENSOR <br />SUMP <br />WALL <br />DIMENSIONS <br />Nr Leads <br />18.5' <br />1.9' Dia <br />MOUNTING SLEEVE CEMENTED TO SUMP WALL <br />JUN( <br />Wo Environmental Products <br />The Leader in Tank Monitoring Technology <br />125 Powder Forest Drive, Post Office Box 2003, Simsbury, CT 06070-2003 TEL: (203) 651-2700, FAX: (203) 651-2719 <br />SUMP <br />WALL <br />AUSTRALIA, Cheltenham, Victoria - BRAZIL. Sao Paulo - ENGLAND- Richmond Surrey - FRANCE: Runyis Cedex - GERMANY: Neuhausen/Filder <br />12370 Replaces 12047 AR2 °0 93 <br />