Laserfiche WebLink
Allk <br /> ANNUAL STILL CONTAINER TES REPORT <br /> TEST DATE: May 23, 2005 <br /> 1. OWNER <br /> Name Quik Stop Markets, Inc. <br /> Address 4567 Enterprise Street Fremont, CA 94538 Phone# 510-657-8500 <br /> Contact Michael Karvelot <br /> 2. FACILITY <br /> Name Quik Stop Market#121 <br /> Address 1196 W. Louise Avenue Manteca, CA 95336 Phone# 510-657-8500 <br /> Contact Michael Karvelot <br /> 3. CUPA <br /> Name San Joaquin County Environmental Health Notified May 12, 2005 <br /> Address 304 E Weber Avenue 3rd Floor Stockton, CA 95202 Phone# 209-468-9847 <br /> Contact Ray Von Flue Fax# 209-468-3433 <br /> Inspector Present Ray Von Flue <br /> 4. TESTING CONTRACTOR <br /> Name Walton Engineering, Inc. Lic# 617238 A, B, Haz <br /> Address P.O. Box 1025, West Sacramento, CA 95691 Phone# 916-373-1152 <br /> Contact Michael Walton Fax# 916-373-1172 <br /> Test Technician Phillip Kingman <br /> 5. TEST RESULTS <br /> Measuring Equipment Used: Caldwell System 2001 /Walton Engineering (Level Change Indicator) <br /> Description Tank#1 Tank#2 <br /> Product contained Gasoline-87 Gasoline-91 <br /> Spill container capacity (US gallons) 5 Gallons 5 Gallons <br /> Spill container manufacturer OPW OPW <br /> Spill container depth (inches) 12.50 13.00 <br /> Is the spill container located in a sump? Yes Yes <br /> Does sump have a liquid sensor installed? No No <br /> Condition of spill container prior to testing Dry Dry <br /> Portion of spill container tested Entire Entire <br /> Depth of water level from bottom (inches) 12.25 12.75 <br /> Wait time for water level to stabilize (hr:min) 0:05 0:06 <br /> Test start time 9:10 AM 9:20 AM <br /> Test end time 9:40 AM 9:50 AM <br /> Test duration (hr:min) 0:30 0:30 <br /> Change in water level (t 0.000 inches) 0.000 0.000 <br /> Pass/Fail threshold (0.005 inches/'/2 Hr.) 0.005 0.005 <br /> TEST RESULT PASS PASS <br /> 6. COMMENTS <br /> Technician Signature Date5 NQS <br /> © 2005 Walton Engineering,Inc. <br />