Laserfiche WebLink
LINE LEAIOETECTOR (LLD) TESfIREPORT <br /> TEST DATE: June 11, 2010 <br /> Al. FACILITY A2. OWNER <br /> Name Quik Stop Market#121 Name Quik Stop Markets, Inc. <br /> Address 1196 W. Louise Avenue,Manteca,CA 95336 Address 4567 Enterprise Street,Fremont,CA 94538 <br /> Phone# 510-657-8500 Phone# 510-657-8500 <br /> Contact Michael Karvelot Contact Michael Karvelot <br /> A3. C U P A A4. TESTING CONTRACTOR <br /> Name San Joaquin County Environmental Health Name Walton Engineering, Inc. <br /> Address 600 E.Main Street,Stockton,CA 95202 Address P.O. Box 1025,W.Sacramento,CA 95691 <br /> Notified June 8,2010 Lic# 617238 A,B,Haz <br /> Inspector Thuy Tran Contact Richard Walton <br /> Phone# 209-468-8257 Phone# 916-825-3203 <br /> I. MECHANICAL LINE LEAK DETECTOR TEST RESULTS <br /> Test Equipment Used: TESTER ERROR <br /> Tank number 1 2 <br /> Product contained Gasoline-87 Gasoline-91 <br /> Leak Detector Type MLLD MLLD <br /> Leak detector make/model FE Petro STP-MLD FE Petro STP-MLD <br /> Serial number Unreadable Unreadable <br /> Functional Element Holding (psi) 18 18 <br /> Resiliency (ml) 75 120 <br /> Test leak rate (gph) 3.00 3.00 <br /> Pump pressure (psi) 28 28 <br /> Metering pressure (psi) 10 10 <br /> Pressure Restriction Reduction (psi) 18 18 <br /> Length of Restriction Test (seconds) 30 30 <br /> Full Flow Opening time (seconds) 5 5 <br /> TEST RESULT PASS PASS <br /> Tank number <br /> Product contained <br /> Leak Detector Type <br /> Leak detector make/model <br /> Serial number <br /> Functional Element Holding (psi) <br /> Resiliency (ml) <br /> Test leak rate (gph) <br /> Pump pressure (psi) <br /> Metering pressure (psi) <br /> Pressure Restriction Reduction (psi) <br /> Length of Restriction Test (seconds) <br /> Full Flow Opening time (seconds) <br /> TEST RESULT <br /> J. COMMENTS: <br /> WALTON <br /> Signature: <br /> ENGINEERING,INC. <br /> Technician: Bruce N.Stewart/A31131 5249892-UT Date: June 11, 2010 <br /> (9 204 u Walton rngineering,Inc. <br />