Laserfiche WebLink
LINE LEAK DETECTOR (LLD) TEST REPORT JUN 0 7 2016 <br />1 <br />TEST DATE: June 2,2016 I <br />AMIMIM <br />Al. FACILITY <br />A2. OWNER <br />Name Quik Stop Market #121 <br />Name Quik Stop Markets, Inc. <br />Address 1196 W. Louise Avenue, Manteca, CA 95336 <br />Address 4567 Enterprise Street, Fremont, CA 94538 <br />Phone # 510-657-8500 <br />Phone # 510-657-8500 <br />Contact Roger Batra <br />Contact Debbie Markovich <br />a i I F. ME$ ME lyj INIM1,01,11-0 M01170 MRS "-Isx <br />A3. C U P A <br />A4. TESTING CONTRACTOR <br />Name San Joaquin County Environmental Health <br />Name Walton Engineering, Inc. <br />Address 1868 E. Hazelton Avenue, <br />Stockton, CA 95202 <br />Address P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified May 18, 2016 <br />Lic # 617238 A, B, Haz <br />Inspector Elena Manzo <br />Contact Veronica Freitas <br />Phone# 209-468-3442 <br />Phone # 916-373-1166 <br />I. LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: <br />Vaporless VMI LDT-890 <br />- <br />. . . . . . . . . . . . . . <br />u <br />Tank number <br />1 <br />2 <br />M <br />Product contained <br />y Gasoline - 87 <br />Gasoline - 91 <br />fT. <br />T Leak Detector Type <br />MLLD <br />MLLD <br />Leak detector makelmodel <br />5 VMI 99LD-2000 <br />FIR Petro STP -MLD <br />Serial number <br />15041292 <br />Illegible <br />Functional Element Holding (psi) <br />28 <br />24 <br />Resiliency (ml)i <br />70 <br />150 <br />Z <br />Test leak rate (gph) <br />3.00 <br />3.00 <br />R <br />ili Pump pressure (psi) <br />28 <br />27 <br />X, <br />111 <br />Metering pressure (psi) <br />17 <br />10 <br />A <br />Alltf <br />, <br />—Pressure Restriction Reduction(psi)11 <br />3 17 <br />Length of Restriction Test (seconds) <br />30 <br />30 <br />Full Flow Opening time (seconds) <br />5 <br />6 <br />TEST RESULT <br />PASS <br />PASS <br />Im <br />V1111"n%-' <br />-'FwF7v7-7-71M1Mw&- <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />a <br />Resiliency (ml) <br />Test leak rate (gph) <br />k <br />Z <br />Pump pressure (psi) <br />R , <br />Metering pressure (psi) <br />-5 <br />" <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />. . ... . . . . .... .. ............... .. <br />. . . . . .. .. ............... . .. ....... <br />on, w"Inwwral <br />J. COMMENTS: <br />WALTON <br />Signature: <br />ENGINEERING, INC <br />Technician: Jessie Wadkins I B36391 6307886 <br />-UT <br />Date: June 2, 2016 <br />