Laserfiche WebLink
Facility: Quik Stop Market #125 <br />Address: 1580 W. Main Street <br />City, state Ripon, CA 95366 <br />Test Date: December 14, 2007 <br />TANK DATA <br />Tank # <br />3 <br />Tank Product <br />Diesel <br />Tank Size finches/ gallons] <br />100.00 <br />8000 <br />Product finches /gallons] <br />45.08 <br />3949 <br />Ullage finches /gallons] <br />54.92 <br />4051 <br />Water in Tank pnches /gallons) <br />0.00 <br />0 <br />Tank Bottom Fm Grade finches 140.00 <br />GROUND WATER DEPTH <br />Ground Water From Grade [" N/A" <br />Method Determined <br />Location <br />PRESSURE SENSOR CALCULATION <br />PSI (1) 45.08 (" product) X 0.031 (Weight product) = 1.397 <br />PSI (2) 0 (" water) X .036 (Water weight) = 0 <br />PSI (3) 1.397 PSI (1) + 0 PSI(2) = 1.397 (Positive head psi) <br />PSI (4) 0 (" water outside) X .036 (Water weight) = 0 <br />PSI (5) 1.397 PSI (3) - 0 PSI (4) = 1.397 <br />PSI (6) Add 0.5 PSI <br />PSI (7) 1.397 PSI (5) + 0.5 PSI ( 6) = 1.897 (Test pressure) <br />TEST EVALUATION <br />ACOUSTICAL TEST RESULTS <br />PASS <br />0 2006 Walton Engineering, Inc. <br />T" Equipment used: EZY 3 Locator Plus <br />Test Method By: Manufacturer <br />Tank Manufacturer. Xerxes <br />T; Mdteltal Double Wall Fiberglass <br />VACUUM <br />Blower Started <br />Test Pressure Reached <br />Blower Stopped <br />Test Began <br />Test Ended <br />Time <br />11:55 AM <br />12:15 PM <br />12:15 PM <br />12:15 PM <br />12:25 PM <br />Pressure <br />0.0000 <br />1.9230 <br />1.9180 <br />1.9140 <br />1.9090 <br />COMMENT ON TEST EVALUATION <br />