Laserfiche WebLink
The following is an itemized list, of underground storage tank violations that have not <br />been addressed for QUIK STOP MARKET #3125 as of March 01, 2017. <br />Open violations from June 10, 2016 inspection <br />Violation #313 - Failure to construct, operate, and maintain primary containment as product -tight. <br />Liquid was observed in UDC 1/2. The designated operator reports dated 2-3-16, 3-16-16, 4-6-16, 5-4-16, and <br />6-1-16, indicated that "fuel is present in UDC 1/2" and requested to correct the leak. All primary containment for the <br />UST system must be tight. Immediately have a properly licensed, trained and certified contractor repair or replace <br />the failed component under permit and inspection of the EHD. This violation, concerning the same UDC, was noted <br />in the June 13, 2014 and June 10, 2015 EHD inspection reports, and is a repeat violation. <br />MA 2 2017 <br />ENVIR <br />ENT t T � 9 E^", B�".9 1 <br />Page 1 of 1 <br />