Laserfiche WebLink
AUG 12 1, <br />TANK <br />ANNULAR <br />1R <br />Test Method By: ® Manufacturer O Industry Standard O Professional Engr. O Other (see below) <br />Test Method Uses: O Pressure • Vacuum O Hydrostatic o Other (see below) <br />Measuring Equipment Used: Vacuum Gauge (range 0 to 30 inches Hg) <br />r)acr-rinfinn Tank 01 Tank #2 Tank 43 <br />Product stored <br />Gasoline - 87 <br />Gasoline - 91 <br />Diesel <br />Tank manufacturer <br />10:10 AM <br />10:55 AM <br />12:15 PM <br />Tank material <br />FRP <br />FRP <br />FRP <br />Tank capacity (US gallons) <br />10,000 <br />10,000 <br />8,000 <br />Is this a multi -compartment tank? <br />No <br />No <br />No <br />Dry or Brine filled annular? <br />Dry <br />Dry <br />Dry <br />Monitoring system show normal annular? <br />Yes <br />Yes <br />Yes <br />Is water table above tank bottom? <br />Unknown <br />Unknown <br />Unknown <br />Was sensor removed for testing? <br />No <br />No <br />No <br />Was sensor properly replaced after testing? <br />N/A <br />N/A <br />N/A <br />Wait time for vacuum to stabilize (hr:min) <br />:10 <br />:10 <br />:10 <br />Test start time <br />10:10 AM <br />10:55 AM <br />12:15 PM <br />Initial vacuum (inches Hg) <br />Test end time <br />10.0 <br />11:10 AM <br />10.0 <br />11:55 AM <br />10.0 <br />1:15 PM <br />Final vacuum (inches Hg) <br />10.0 <br />10.0 <br />10.0 <br />Test duration (hr:min) <br />1:00 <br />1:00 <br />1:00 <br />Change in vacuum (inches Hg) <br />Pass/Fail threshold (inches Hg / hour) <br />0.0 <br />2.0 <br />0.0 <br />2.0 <br />0.0 <br />2.0 <br />TEST ULT <br />PASS <br />PASS <br />PASS <br />0 2016 Walton Engineering, Inc. <br />