SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer Industry Standard Professional Engineer <br /> L�Other(Specify) <br /> Test Method Used: Pressure X Vacuum Hydrostatic <br /> C7 Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - '/2"x-30"Hg. <br /> 11 ON= <br /> Tank# 1 Tank#2&3 Tank# Tank# <br /> Is Tank Exempt From Testing? No No <br /> Tank Capacity: 12K 12K Split 6/6 <br /> Tank Material: Glass/Steel Glass/Steel <br /> Tank Manufacturer: Trusco Trusco <br /> Product Stored: Regular 87 Supreme 91/Diesel <br /> Wait time between applying 5 Minutes 5 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 12:20 12:25 <br /> Initial Reading(Rj): -10"Hg. -10"Hg. <br /> Test End Time: 1:20 1:25 <br /> Final Reading(RF): -10"Hg. -10"Hg. <br /> Test Duration: 1 Hour 1 Hour <br /> Change in Reading(RF-Ri): 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. No loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? No No <br /> Was sensor properly replaced and NA NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />