Laserfiche WebLink
HAZARDOUS MATERIAL MAN ENT PLAN <br />DEALER: Billie D. Parks <br />MONITORINKLAN <br />OWNER: CHEVRON, U.S.A. <br />_BUSINESS NAME: Bill's Chevron <br />P.O.BOX 5004 <br />STREET: 6633 Pacific Ave SAN RAMON, CA 94583-0804 <br />-- CITY: Stockton , CA ZIP: 95207 <br />— --- . STATION NO: 96171, <br />SITE PHONE # 292-42-7-4115 <br />DUNN & BRADSTREET # 00-138-2555 SIC CODE:,5541_ 541 7538 <br />BUSINESS: <br />--GASOLINE SALES_ AUTO REPAIR_ XX CAR WASH FOOD MART_ <br />'EXISTING UNDERGROUND TANKS ARE AS FOLLOWS: <br />No. of SIZE MATERIAL <br />TANKS (gal) (STL/FG) <br />SUPER UNLEADED 1 10.000 EG <br />REGULAR UNLEADED 1 10.000 FG <br />FG <br />FG <br />CONST .- SPILL OVERFILL <br />(SW/DW) (YIN) (YIN) <br />DW <br />Y <br />Y <br />DW <br />Y <br />Y <br />DW <br />Y _ <br />Y A <br />DW Y Y <br />'_..:.PRODUCT LINES: MATERIAL: FG <br />77CONSTRUCTION: Double Wall <br />LINE- -LEAK DETECTION METHOD: ELECTRONIC X MECHANICAL <br />All -product lines have line leak detectors capable of detecting a leak of <br />3 gallons or more per hour at 10 lbs. per square inch line pressure <br />;within 1 hour,• see page one for -a -description of -the equipment installed <br />at --this location.. <br />All -product lines -are pres.surized.using a submerged pumping system and <br />are tested annually -to assure the -leak -detectors are functional.Impact <br />'valves are also inspected annually to assure closure. <br />Repair_ -and/or replacement of all--leak-detectors-and. imp act valves -.will -.be. <br />d®ne' annually- at=_the_ time of_._inspection and -retested to meet the above <br />test-- conditions. <br />W <br />This -document is to be kept -current: -and -at- the= site: -Revision- 8 =1991 <br />