n <br />SWRCB, January 2002 <br />E <br />Page of <br />7. U1�llEK-lll�Y1+1V�1 K (U1V 1A1Pl1V11 PI1 UUl 1L' Slllrla <br />Test Method Developed By: <br />❑ UDC Manufacturer <br />❑ Industry Standard <br />X Professional Engineer <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />El Other (Spec) <br />Yes <br />Yes <br />Test Method Used: <br />❑ Pressure <br />❑ Vacuum <br />X Hydrostatic <br />Not Alarmed <br />❑ Other (Spec) <br />Is system programmed for fail- <br />safe shutdown?* <br />Yes <br />Test Equipment Used: Caldwell Level Change Indicator <br />Yes <br />Equipment Resolution: .002 <br />Was fail-safe verified to be <br />o erational?* <br />UDC # 1&2 <br />UDC # 3&4 <br />UDC # 5&6 <br />No <br />UDC # 7&8 <br />UDC Manufacturer: <br />Bravo <br />Bravo <br />Bravo <br />Test Start Time: <br />Bravo <br />UDC Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />.001 <br />Fiberglass <br />UDC Depth: <br />25" <br />25" <br />25" <br />10:57 <br />25" <br />Height from UDC Bottom to Top <br />12" <br />12" <br />12" <br />.001 <br />12" <br />of Highest Piping Penetration: <br />Height from UDC Bottom to 6" 6" 6" 6" <br />Lowest Electrical Penetration: <br />Condition of UDC prior to Dry Dry Dry Dry <br />Portion of UDC Tested' <br />Water Level 14" <br />Water Level 14" <br />Water Level 14" <br />Water Level 14" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />Yes <br />Yes <br />Yes <br />Yes <br />Turbine shutdown response time <br />Not Alarmed <br />Not Alarmed <br />Not Alarmed <br />Not Alarmed <br />Is system programmed for fail- <br />safe shutdown?* <br />Yes <br />Yes <br />Yes <br />Yes <br />Was fail-safe verified to be <br />o erational?* <br />No <br />No <br />No <br />No <br />Wait time between applying <br />water and starting test <br />5 Minutes <br />5 Minutes <br />See Comments <br />5 Minutes <br />Test Start Time: <br />9:52 <br />10:27 <br />10:32 <br />10:37 <br />Initial Reading (RI): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />10:22 <br />10:57 <br />11:02 <br />11:07 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading RF-Rj: <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Pass <br />Pass <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Yes <br />Yes <br />Yes <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />/11 F P i 0 2011-i; <br />M1EN- AL HEALTH <br />DEPARTMENT <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />