Laserfiche WebLink
1115000 Field Test Apparatus <br />.gTanknology Line Leak Detector Test <br />Work Order: <br />Site Name / ID: <br />Address: <br />City: <br />2314881 <br />CHEVRON # 96171 (N-621-1-3) / 96171 <br />6633 PACIFIC AVE <br />STOCKTON <br />Page 1 of 1 <br />Date: 1/30/2014 <br />State: CA Zip: 95207 <br />Tank ID <br />T1 <br />regular 1 <br />T1 regular 1 <br />Product <br />SUPREME <br />REGULAR <br />SUPREME REGULAR <br />Product Line <br />1 <br />1 <br />1 1 <br />Tested From <br />4 <br />4 <br />4 4 <br />Existing/New <br />Existing <br />Existing <br />Existing Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />Electronic Electronic <br />Manufacturer/Model <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Veeder Root PLLC Veeder Root PLLD <br />erial No. <br />GC 8006 <br />005609 <br />GC 8006 005609 <br />ump Operating Pressure (psi) <br />32.00 <br />37.00 <br />32.00 37.00 <br />alibrated Leak (ml/min) <br />189.0 <br />189.0 <br />189.0 189.0 <br />alibrated Leak (gph) <br />3.00 <br />3.00 <br />3.00 3.00 <br />Holding PSI <br />N/A for Electronic Lo's <br />Resiliency (ml) <br />N/A for Electronic Lo's <br />Metering PSI <br />N!A for Electronic Lo's <br />Opening Time (sec) <br />N/A for Electronic Lo's <br />Lest Results <br />Fail <br />Fail <br />Pass Pass <br />Technician Comments: both Id failed first test, syphon jet valves were replaced, air was pumped out of the lines and the I.d. <br />passed. <br />Technician Name: <br />Technician Signature: <br />Jarrod Cooke Certification #: 1352 <br />I Expire Date: 2/10/2015 <br />Environmental Compliance for Petroleum Systems <br />® 2014 TanlmolM Inc., Austin, Tx. All rights reserved. tanknology.corn <br />