Country Mart Tracy <br />Repair list <br />UDC 1-2 <br />No repairs made <br />UDC 3-4 <br />13oot clamps were loose and allowed water to run out of box. Water was going <br />from UDC back to the piping sumps. Boots were pulled back c1med and reset into <br />place, There was a leaking electrical penetration that was removed and replaced with a <br />Blue Line replacement boot. <br />UDC 5-6 <br />Water was going through secondary lines into piping sumps. Boots were pulled <br />back and cleaned with acid tone and reset. Water was also going into the Electrical J - <br />Boxes. Once the water levcl went bellow the lids of the boxes the UDC held all water is <br />side. <br />UDC 7-8 <br />No repairs made - <br />UDC 9-10 <br />Was unable to get water to hold because electrical lines would not seal off, still <br />trying to find some way of isolating lines so testing can be competed. <br />UDC 11 S. <br />No repairs made - <br />UDC 11-12 <br />Unable to locate leak, need to remove concrete and expose box to find where <br />water is going. <br />UDC 12Sat-13 <br />No repairs made. <br />UDC 13-14 <br />There was a bad electrical penetration that was replaced with a Blue Line <br />replacement boot. On one of the piping penetrations all of the nuts that held the <br />petIL5YAM7YU-&&-SMY w2x yat -*.q <br />.0M.?metration was not sealinp,, off <br />on to the sump wall. <br />2'd BET 01?917: 01 6698929602 DAS 3NI19UN0S'8G:W0NJ uos:eo 9002-c2-9nu <br />