Laserfiche WebLink
Page of <br />. - # <br />Test Method Developed By: <br />4. SPILL/OVERFILL CONTAINMENT BOXES <br />0 UDC Manufacturer X Industry Standard <br />0 Other (Specify) <br />0 Professional Engineer <br />Test Method Uses: <br />0 Pressure 0 Vacuum <br />0 Other (Specify) <br />X Hydrostatic <br />Measiuing uipment Used for Testing: INCON TS -STS V2.1 <br />Spill Box # DI Fill Spill Box # <br />Bucket Diameter: 20" <br />Spill Box # <br />Bucket Depth: <br />16" <br />Wait time between applying <br />presswWvacuum/water and <br />starting test: <br />15 Min. <br />Test Start Time: <br />9:40 <br />Initial Reading W: <br />5.1293" <br />Test End Time: <br />9:55 <br />Final Reading (Rf): <br />5.1290" <br />Test Duration: <br />15 Min. <br />Change in Reading GRf-R.�: <br />0.0003" <br />P&%,.Tafl Threshold: <br />0.0029' <br />Test Result: Pass <br />Comments — (include information on repairs made to facilitate a passing lest and indicate whether a <br />permit was obtained for the repairs) <br />— <br />All Hydrostatic test <br />performed twig to insure testing results <br />R-C.U.S.T.COM January 2004 <br />