Laserfiche WebLink
` .1 Page of <br />Test Method Developed By: <br />X Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Uses: <br />❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Measuring Equipment Used for Testing: <br />Tank Capacity: 7 <br />Liquid Filled Gauge 1% Dial Span Accuracy <br />Tank # 1 Tank # Tank # <br />12,000 <br />Tank Material: <br />Fiberglass / Steel <br />Tank Manufacturer: <br />Modem <br />Product Stored: <br />Diesel <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />15 Min. <br />Test Start Time: <br />1200 <br />Initial Reading (RO: <br />10" Vacuum <br />Test End Time: <br />1300 <br />Final Reading (RF): <br />10" Vacuum <br />Test Duration: <br />I Hour <br />Change in Reading (RF -RI): <br />0 <br />Pass/Fail Threshold: <br />0 <br />Test Result: <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced after <br />testin ? <br />Yes <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />R.C.U.S.T.COM December 2001 <br />