Laserfiche WebLink
ULLAGE TESTING DATA <br /> Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Product: DIESEL <br /> True Capacity: 3j,500 <br /> Ullage volume: 295 <br /> Fluid pies-sure <br /> on tank bottom(PSI) : 1.97 <br /> Test Ullage <br /> pressure (PSI) : 2 <br /> Stabilization time <br /> (minutes) : <br /> 2 <br /> Fill start time: 20:40 <br /> Time to I PSI: I <br /> Time to test <br /> pressure: I <br /> Start time - test 1 20:44 <br /> Nitrogen flow (cubic <br /> feet per hour/CFH) : 0.20 <br /> Ullage temperature: 76.2 <br /> finish time - test 1: 20:54 <br /> Nitrogen flow (CFH) : 0.00 <br /> Start time - test 2: 20:55 <br /> Nitrogen flow (CFH) : 0.20 <br /> Ullage temperature: 76.1 <br /> Finish time - test 2: 21:05 • <br /> Nitrogen flow (CFH) : 0.00 <br /> Start time test 3: <br /> Finish time test 3: <br /> Nitrogen Flow (CFH) : <br /> Pass/Fail: PASS <br /> page 3 <br />