Laserfiche WebLink
• 0 <br /> WESTERN AMERICA TANK TESTING, INC. <br /> **** CERTIFICATE OF UNDERGROUND STORAGE TANK INTEGRITY *** <br /> PRECISION VOLUMETRIC QUAN`1':ITA.TIVE VOLUMETRIC LEAK TEST <br /> WESTERN AMERICA TANK 'TESTING, INC . has tested the following <br /> underground storage tank systems , and certifies them tight at the <br /> product height. equal to the grade level . <br /> List of Tank Systems Tested: <br /> TANK CONTENTS 'TANK CAPACI`T'Y. TANK NUMBER STATION NUMBER, <br /> Diesel 3 , 500 gal . Diesel UE046 <br /> TANK LOCATION: PACIFIC BELI. <br /> 907 Linr_oln Road <br /> Stockton , California 95207 <br /> WESTERN AMERICA TANK TESTING , INC . is authorized to test and <br /> certify these tanks using the VPLT Tank Testing System by the <br /> manufacturer, NDE Technology, Inc . <br /> This certification meets or• exceeds certification standards set by <br /> the State of California, Federal and the Local jurisdictional <br /> agency: County of San Joaquin . <br /> WESTERN AMERICA TANK TESTING , INC . CERTIFICATION meets the <br /> requirements of California Administrative Code Title 2:3 Water <br /> Resources Control Board, Subchapter 16 Underground Storage <br /> Regulations , Part 2643 . The leak test: certifies the leak <br /> resolution of instrumentation or allowable change is no more than <br /> 0. 05 gallons per hour• as cited in Part 2643 (b) on Page 4 . 14 . <br /> Date 08/13/1991 <br /> Certification No. 891665 <br /> Certified Tester ; Shawn Hoppes <br /> License Number 92-- 1129 <br /> Recertification Date recommended: 08/13/1.992 <br /> WESTERN AMERICA TANK TESTING , INC . , Bakersfield , CA ( 805 ) 322--9827 <br />