1 <br />Pacific Bell: 2600 Camino Ramon, Room 3E000, San Ramon, CA 94583 <br />ROUTINE MONITORING PROCEDURES <br />Section 2632 (d)(1) Title 23 CCR, Chapter 16 <br />Facility Name: Pacific Bell (UE046) <br />Facility Address: 907 LINCOLN ROAD, STOCKTON <br />UST Installed: Double Wall Composite 4,000 Gallons Containing Diesel Fuel for the Emergency <br />Generator. <br />Piping Installed: Double Wall "Bnviroflex" non-metallic flexible piping system for the product <br />supply and return lines. <br />A. The Frequency of Performing the Monitoring: <br />Double wall UST Interstitial space and its two sumps. <br />B. The methods and equipment used to perform continuous monitoring are: <br />VEEDER ROOT UST Monitoring System Model # TLS -350 <br />External modem <br />• GPH magnetostrictive in -tank volumetric probe Model # 847390-107 <br />Floating liquid sensors in the: <br />1. UST Annular space sensor Model # 794390-407 <br />2. Piping sump sensor Model # 794380-352 <br />3. Tank Overfill Model # 790091-001 <br />4. Fill sump sensor Model # 794380-352 <br />L\HAZMATVACBELL\FORMS\SBC Monitor Pian Merge.doc <br />Printed: December 6, 2001 page 2 <br />