Laserfiche WebLink
CALIFORNIA HAMRDOUS SERVICES, INCI, <br />Station# CHP - Stockton Date: 1-8-09 <br />Address: 3330 N. Ad Art Rd., Stockton, CA 95215 <br />Test Information <br />Comments: <br />This letter certifies that the annual leak detector tests were performed at the above referenced <br />facility according to the equipment manufacturers procedures and limitations and the results <br />as listed are to my knowledge true and correct. The mechanical leak detector test pass/fail is <br />determined using a low flow threshold flow rate of 3 gph at 10 PSI. <br />Inspected By: Contractor: California Hazardous Services, Inc. <br />Technician: Brian Halfwassen Lic# 734854 <br />Signature: /-A / <br />1 <br />2 <br />3 <br />4 <br />5 <br />Product <br />87 <br />Manufacturer <br />FE Petro <br />Model <br />STP -MLD <br />Model Number <br />Full Operating Pressure (psi) <br />26 <br />Line Bleed Back (ml) <br />110 <br />Trip Time (sec) <br />3.2 <br />Metering Pressure (psi) <br />10 <br />RE Holding Pressure (psi) <br />18 <br />Test Leak Rate (ml/min) (gph) <br />3.0 <br />PASS or FAIL <br />Pass <br />Comments: <br />This letter certifies that the annual leak detector tests were performed at the above referenced <br />facility according to the equipment manufacturers procedures and limitations and the results <br />as listed are to my knowledge true and correct. The mechanical leak detector test pass/fail is <br />determined using a low flow threshold flow rate of 3 gph at 10 PSI. <br />Inspected By: Contractor: California Hazardous Services, Inc. <br />Technician: Brian Halfwassen Lic# 734854 <br />Signature: /-A / <br />