Laserfiche WebLink
INVOICE #AT000041 <br />AFFORDA-TE$T <br />PO BOX 36 <br />THORNTON, CA. 95686 <br />(209)794-2470 or (800)524-9087 <br />TANK STATUS REPORT -- iG TEST <br />--------------------------------- <br />***** CUSTOMER DATA ***** <br />D & D MINI -MART <br />14971 N. HWY. 88 <br />LODI, CA. <br />95240 <br />TEST DATE: 09/13/94 <br />***** SITE DATA ***** <br />D & D MINI -MART <br />14971 N. HWY. 88 <br />LODI, CA. <br />95240 <br />CONTACT: MUNRO, DON CONTACT: MUNRO, DON <br />PHONE #: 209 369-1844 PHONE #: 209 369-1844 <br />***** COMMENT LINES ***** <br />REG UNLD HAS SUB. PUMP, DIE. AND PLUS ARE SUC. <br />CURRENT EPA STANDARDS DICTATE <br />THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br />OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br />TANK #1: DIESEL FUEL 2 TYPE: STEELMM '>.16 <br />TANK IS TIGHT. <br />11 W-7 <br />TANK #2: PLUS UNLEADED TYPE: STEEL <br />TANK #3: REG UNLEADED TYPE: STEEL' .04 <br />TANK IS <br />TIGHT., <br />bTT 1_ '%�-Q 1 -1143 <br />OPERATOR: - ��� - � � - SIGNATURE: DATE: <br />-9-:: <br />_i a 7Y <br />