Laserfiche WebLink
TanMwkogy <br />Test Date: 11/01/2002 <br />SECONDARY CONTAINMENT TEST RESULTS Work order. 2224367 <br />SI IMP TFSTS <br />Type <br />Tank or Disp <br /># <br />Manufacturer <br />Model or <br />Material <br />Diam./Width/Length <br />(" ) <br />Depth <br />(11 ) <br />Test Method <br />Start <br />Time <br />Initial <br />Level <br />Level <br />Chane <br />Finish <br />Time <br />Final <br />Result <br />Pass/ <br />Fail <br />STP Sump <br />SUP <br />Western Fiberglass <br />Fiberglass <br />36" <br />53 <br />Hydrostatic-VPLT <br />1129 <br />18" " <br />.00008 <br />1200 <br />.001 gph <br />Pass <br />STP Sump <br />REG <br />Western Fiberglass <br />Fiberglass <br />36 <br />48 <br />Hydrostatic-VPLT <br />1017 <br />18 " <br />-.0180 <br />1048 <br />-.281 gph <br />Fail <br />Dispenser Sump <br />1/2 <br />Plastic <br />15X40 <br />10 <br />Hydrostatic-VPLT <br />1046 <br />7 <br />-.0184 <br />1100 <br />-.438 gph <br />Fail <br />Dispenser Sump <br />3/4 <br />Plastic <br />15X40 <br />10 <br />Hydrostatic-VPLT <br />1023 <br />7 " <br />-.00010 <br />1039 <br />-.002 gph <br />Pass <br />Comments: <br />