Laserfiche WebLink
Continued UNDERGROUND STORAGE TANK (UST) PROGMAM INSPECTION REPORT <br /> Facility Address: 1617 W FREMONT ST.,STOCKTON CA Inspection Date: 4/22/2008 <br /> ROUTINE AND MONITORING SYSTEM CERTIFICATION UST INSPECTION REPORT <br /> #26. ANNUAL LINE LEAK DETECTOR TESTING <br /> THE ELECTRONIC LINE LEAK DETECTOR FOR THE PREMIUM 91 GASOLINE PRODUCT FAILED THE THREE GALLON PER HOUR <br /> LEAK TEST. OBTAIN PERMIT APPLICATION WITHIN TWENTY FOUR HOURS AND THE REPAIR/REPLACMENT MUST BE MADE <br /> WITHIN 48 HOURS. WORK CAN BE PERFORMED WITHOUT A APPROVED PERMIT. CORRECT IMMEDIATELY. <br /> SUBMIT THE RETURN TO COMPLIANCE CERTIFICATION WITH A CORRECTIVE ACTIONS STATEMENT AND SUPPORTING <br /> DOCUMENTATION. SUBMIT BY 5/22/08 <br /> NOTE:ALL EHD STAFF TIME ASSOCIATED WITH FAILY TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE <br /> CURRENT HOURLY RATE($98.00). <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> EHD Inspectar:, d By: Title: <br /> Ray von Flue. G <br /> San Joaquin County Environmental Health Department • 600E Main Street,Stockton CA 95202 • (209)468-3421 <br /> EHD 23-02-002 Page 2 <br /> 3/13/2008 <br />