Laserfiche WebLink
bp BP West Coast Products LLC rC 1 <br /> 4 Centerpointe,LPR 4-440 I J <br /> La Palma,California 90623 LI 11 �J <br /> Mailing Address:Box 6038 JUN 2 1 2006 <br /> Artesia,CA 90702-6038 is <br /> Voice(800)525-5857 x6233 E NVI R O N V1,DW HEALTH <br /> Fax(714)670-5420 PERMIT/SERVICES <br /> Email schettji@bp.com <br /> June 20,2006 <br /> VIA FED EX <br /> Ms. Lori Luces Tracking# 79213141 8233 <br /> Environmental Health Department <br /> San Joaquin County <br /> 304 E. Weber Avenue, 3rd Floor <br /> Stockton, CA 95202 <br /> RE: Inspection Report <br /> ARCO No. 5450 <br /> 1617 W. Fremont <br /> Stockton, California <br /> Dear Lori Luces: <br /> This letter responds to the UST Program Inspection Report conducted by the San Joaquin <br /> County Environmental Health Department(EHD), dated May 31, 2006, for the ARCO <br /> facility identified above. <br /> 1. Alleged Violation: The UST Program inspection report stated, "#11. The following <br /> sensors were not properly located to detect a leak: <br /> • 91 fill sump sensor was located in the middle of the sump <br /> 87 slave fill sensor located about 4 inches from the bottom <br /> • 87 master fill sensor located about 1 foot from the bottom <br /> • Dispenser pan'/4 sensor located about 4 inches from gthe bottom. <br /> Ensure all sensors are properly located to detect a leak at the earliest possible <br /> opportunity. Correct immediately". In the corresponding violation checklist,a <br /> check was placed next to"CCR 2630(d), UST system monitoring equipment is <br /> properly located to detect a leak." <br />