Laserfiche WebLink
Up <br /> Line Leak Detector Test Data Sheet <br /> Station##5450 Date 10/3/ 2008 <br /> Address 1617 W. Freemont St. <br /> Stockton, Ca <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer Red Jacket Red Jacket <br /> Model CPT FX 1 V <br /> Full Operating Pressure(psi) 34 33 <br /> Line Bleed Back(ml) 76 148 <br /> Trip Time(sec) N/A 2 <br /> E <br /> Metering Pressure(psi) N/A 13 <br /> F/E Holding Pressure(psi) 23 26 <br /> 1 <br /> Test Leak Rate (ml/min)(gph) 189/3GPH 189/3GPH <br /> PASS or FAIL Pass Pass <br /> Comments: 91 CPT leak detection turned off to enable use of variable <br /> speed turbine. CPT failed in previous years,no parts.There mechanical i <br /> LD installation. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility . <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> i <br /> Inspected By: Contractor_Tait Environmental Services <br /> Technician Dra an Pesic Lic#5240928-UT <br /> Signature •��°-C . <br />