Laserfiche WebLink
bp <br /> 01 <br /> v <br /> LINE LEAK DETECTOR TEST <br /> Facility : Arco 5450 Date: 09/23/10 <br /> Address: 1617 W Fremont St. <br /> City, State: Stockton, CA 95203 <br /> Testing Information <br /> 1 2 3 4 5 <br /> Product: 87 Main 91 <br /> Manufacturer Red Jacket VR <br /> Leak Detector Serial Number un readable unreadable <br /> Leak Detector Model No. CPT FXIV <br /> Full Operating Pressure (psi): 35 38 <br /> Test Leak Rate(ml/min)(gph) 3.00 3.00 <br /> Bleed Back Rate(ml): <br /> Turbine Holding Pressure (psi): 21 22 <br /> Metering Pressure(mechanical only): 10 <br /> Open/Trip Time(mechanical only): 1 min. <br /> Pass/Fail Pass Pass <br /> Comments: 87 main has an Electronic and 91 has a Mechanical. <br /> Note: Pass= Leak detector reads leak and meters line. <br /> Fail= Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The mechanical leak test <br /> detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Wayne Perry 30 Main Ave Sacramento CA <br /> Technician: Brandon Smith Lic#: 300345 <br /> Signature: 'C`•� <br />