Laserfiche WebLink
aNIt-NIUAN UUNTAiNMEN1 PAGE 02 <br />Tea port No. 57.6-8703 <br />PagdWof 2 <br />National Scientific Testing Division <br />Technical Services 1536 East Valencia Drive <br />Syst9ms Group Fullerton. Calilcrnie 92631 <br />Tei; 714 879 6110 <br />26 May 1998 <br />FULLERT4N DIVISION RBPOR7 376—g703-1 <br />American containment Purchase Order Number 077 <br />A. TL' a7TEST: <br />B. Ifrt : <br />C. SPECIFIC TIONS: <br />D. TEST _RKsULTS: <br />Leakage <br />Fuel Containment BOX, AMCOM Elite <br />Dispenser Drip Pan <br />I. Verbal instructions from <br />American containment <br />2. MIL -STD -45662A <br />3. MIL -1-45208A, Amendment I <br />The fuel containment box was completely filled with water <br />and observed for leakage of a 24-hour period. <br />There was no visible evidence of leakage, deformation or <br />damage noted following the 24-hour period. <br />The Fuel Containment Box was drained and returned to <br />American Containment for final evaluation. <br />NATIONAL TECHNICAL, SYSTEMS <br />T. P. Smith, etty tteson, <br />Program Manager Qual' Assuranc Mztnager <br />We report sod *e khre"doo ftnuh as harein reptoorac tie t of teethes %A exWen ida rMW sad aelerted by die cliene performed to tptailimtkn, <br />and/or prMadams cele„ ted by the eliwL Naim Tedtmiad 3yekmr (HTS) mates evRerad or i�pLod that svcb te�nng is esiegwca or <br />iaedagwte) to demoaabate effiei.oscy, pe.for�neg. reliability. ae any QdW ' of da artider being fated, or sine& prodacte. IU report *MW <br />not be relied .goo as on endorsement or artiPaatioa by N73 of the equipment treed. nor 4098 it repraaees My etd—uA mbebaarer r to if.--4—tabXW or <br />f bum of 4.98 tag crock or similar prodwb fat <br />