TK-TEK RECEIVED <br /> TAWTEK ENVIRONMENTAL CORPOR.ATI <br /> APR 0 9 2014 <br /> ENVIRONMENTAL <br /> HFAUH <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: 3/27/2014 Work Order# 14032602-7 <br /> Location: SOUTH BAY TIRE Contact: MIKE ELIASON <br /> 1501 IN CHARTER WAY <br /> STOCKTON CA 95206 Telephone: (209)948-9412 <br /> SUMP# 3/4 5/6 <br /> PRODUCT 87 DIESEL <br /> LD TYPE Mechanical, (W)PLL D, (P)LLD I M M <br /> LD MANUFACTURER FE PETRO VMI <br /> LD MODEL MLD STP LD2000 <br /> LD SERIAL NUMBER 04080026 08031181 <br /> SUMP CONDITION DRY DRY <br /> RESILIENCY 150 ML 150 ML <br /> OPERATING PRESSURE 26 PSI 30 PSI <br /> OPENING TIME 3 SEC 4 SEC <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 12 PSI 12 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A <br /> LD PASS OR FAIL? PASS PASS <br /> Comments: <br /> Technician: RICHARD THOMAS Contractor Lic. # 803705 <br /> Signature: " s <br /> PO BOX 5850,RIVERSIDE,CA 92517-5850 TEL 951-779-4999 FAX 951-788-7089 <br /> WWW,TANK-TEK.COM <br />