Laserfiche WebLink
Ll <br />Secondary Containment Testing Report Form - Page 3 of 5 <br />F. Testing of Piping Sumps/Turbine Sumps <br />❑ N/A (No piping/turbine sumps) <br />Test Method Developed By: ® Sump Manufacturer; ❑ Industry Standard; ❑ PE; ❑ Other (Specie): <br />Test Method Used: ❑ Pressure; ❑ Vacuum; ® Hydrostatic; ❑ Other (Spec): <br />Test Equipment Used: Incon TS -STS <br />Equipment Resolution: 0.001" <br />Sump #: Diesel STP <br />I Sump #: 87 STP <br />Sump #: <br />Sump #: 4 <br />Sump Diameter (inches): <br />42 <br />42 <br />Sump Depth (inches): <br />48 <br />48 <br />Sump Material: <br />FRP <br />FRP <br />Height from Tank Top to Top of <br />Highest Pipe Penetration (inches): <br />16" <br />16" <br />Height from Tank Top to Lowest <br />Electrical Penetration (inches): <br />28" <br />28" <br />Portion of Sump Tested: <br />Bottom Half <br />Bottom Half <br />If turbine shuts down when sump <br />sensor detects liquid, specify <br />turbine shutdown response time. <br />[I N/A <br />minutes. <br />171 N/A <br />minutes. <br />El N/A <br />minutes. <br />❑ N/A <br />minutes. <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 minutes. <br />15 minutes. <br />minutes. <br />15 minutes. <br />Test Start Date/Time: <br />1:58 3:09 <br />2:19 3:09 <br />Initial Reading (Rj): <br />5.859 5.857 <br />2.305 2.316 <br />Test End Date/Time: <br />2:14 2:34 <br />2:34 3:24 <br />Final Reading (RF): <br />5.859 5.857 <br />2.307 2.318 <br />Change in Reading (RF — RI): <br />0.00 0.00 <br />0.002 0.002 <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />0.002 <br />Test Result: <br />® Pass; ❑ Fail <br />® Pass; ❑ Fail <br />❑ Pass; ❑ Fail <br />❑ Pass; ❑ Fail <br />Was leak detection sensor <br />properly replaced and verified as <br />functional after testing? <br />® Yes; ❑ No; <br />❑ N/A (Not Removed) <br />® Yes; ❑ No; <br />❑ N/A (Not Removed) <br />❑ Yes; ❑ No; <br />❑ N/A (Not Removed) <br />❑ Yes; ❑ No; <br />❑ N/A (Not Removed) <br />G. Testing of Under -Dispenser Containment (UDC) <br />❑ N/A (No dispensers or no UDC) <br />Test Method Developed By: ® UDC Manufacturer; ❑ Industry Standard; ❑ PE; ❑ Other (Spec): <br />Test Method Used: ❑ Pressure; ❑ Vacuum; ® Hydrostatic; ❑ Other (Spec): <br />Test Equipment Used: lncon TS -STS I Equipment Resolution: 0.001 <br />UN -054 - 315 www.unidoes.org 02/26/02 <br />