Laserfiche WebLink
tTANK-W <br /> TANK-TEK ENVIRONMENTAL CORPORATION <br /> MAR 2 5 2016 <br /> 'WIRONIVIENTAI <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION,SHEET <br /> Date: 311112016 Work Order# 16031101-7 <br /> Location: -CHARTER WAY Contact: MIKE ELIASON <br /> 1501 IN CHARTER WAY <br /> STOCKTON CA 95206 Telephone: (209)948-9412 <br /> SUMP# 3/4 516 <br /> PRODUCT 87 DIESEL <br /> LD TYPE[(Mechanical,(W)PLLD, (P)LLD I M M <br /> LD MANUFACTURER FE PETRO VMI <br /> LID MODEL MLD STP LD2000 <br /> LD SERIAL NUMBER 104680026 08031180 <br /> SUMP CONDITION DRY DRY <br /> RESILIENCY 100 ML 150 IVIL <br /> OPERATING PRESSURE 26 PSI 30 PSI <br /> OPENING TIME 4 SEC 4 SEC <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 22 PSI 20 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A NIA <br /> LD PASS OR FAIL? PASS PASS <br /> Comments: <br /> Technician: RICHARD THOMAS Contractor Lic. # 803705 <br /> Signature: <br /> PO BOX 5850,RIVERSIDE,CA 92517-5850 TEL 951-779-4999 FAX 951-788-7089 <br /> WWW.TANK-TEK.COM <br />