Laserfiche WebLink
UNDER DISPEAER CONTAINMENT (#CC) TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: o Pressure o Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />Description <br />Disp # 1/2 <br />ulsp IF s14 <br />UDC manufacturer <br />Bravo <br />Bravo <br />UDC material <br />Steel <br />Steel <br />UDC depth (inches) <br />9 <br />9 <br />Height from UDC bottom to highest <br />piping penetration <br />Bottom <br />Bottom <br />Height from UDC bottom to lowest <br />electrical penetration <br />Bottom <br />Bottom <br />Condition of UDC prior to testing <br />Dry <br />Dry <br />Portion of UDC tested <br />Entire <br />Entire <br />Type of shut -down present <br />Float <br />Float <br />Was sensor removed for testing? <br />N/A <br />N/A <br />Was sensor properly replaced after testing? <br />N/A <br />N/A <br />Depth of water level from UDC bottom (in.) <br />6 <br />6 <br />Wait time for water level to stabilize (hrmin) <br />0:10 <br />0:10 <br />Test start time <br />11:14 AM <br />10:55 AM <br />Initial Probe Reading <br />0.2997 <br />0.3943 <br />Test end time <br />11:29 AM <br />11:10 AM <br />Final Probe Reading <br />0.2998 <br />0.3962 <br />Test duration (hr.min) <br />0:15 <br />0:15 <br />Change in water level (± 0.0000 inches) <br />0.0001 <br />0.0019 <br />Pass/Fail threshold (±0.0020 inches / ; Hr.) <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />Comments: <br />0 2006 Walton Engineering, Inc. <br />