Laserfiche WebLink
ITTO <br /> &, Inc. <br /> t T T Sy <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 24, 19.89 <br /> APR 2 6 1989 <br /> CITY OF STOCKTON ENVIRONMENTAL HEALTH <br /> :465 South Lincoln Street PERMIT/SERVICES <br /> Stockton, California 95205 <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight, according to the current <br /> rules , if the gain is lass than .02 or the loss is less than . .05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action.' <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> #5 1 ,000 Motor Oil •• .02337 Yes <br /> #6 2 ,000 Hyd, Oil + . 00643 Yes <br /> e <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> e _ <br /> rank Kese <br /> Certified ter - <br /> 800 262-8378 166 Frcmk Circle Stocktou. CA,95 46641M,l <br />