Laserfiche WebLink
A <br />11 <br />SWRCB. January 2002 <br />CITY OF STOCKTON <br />CORP YARD <br />June 25, 2004 <br />Ll <br />Page 7 of 7 <br />Facility is Not Equipped With Spill/Overfill Containment Boxes [ ] <br />Spill/Overfill Containment Boxes are Present, but were Not Tested <br />Test Method Developed By: [ ] Spill Bucket Manufacturer [X ] Industry Standard [ ] Professional Engineer <br />Other S eci <br />Test Method Used: [ ] Pressure [ ] Vacuum [X ] Hydrostatic <br />Other (Specify) <br />Test Equipment Used: Equipment Resolution: <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />SYSTEM PASSED <br />Spill Box #1 Unlead <br />Spill Box #2 Diesel <br />Spill Box # <br />Spill Box # <br />Bucket Diameter: <br />13" <br />13" <br />Bucket Depth: <br />14-1/2" <br />16-1/2" <br />Wait time between <br />applying <br />5 Minutes <br />5 Minutes <br />pressure/vacuum/water and <br />starting test: <br />Test Start Time: <br />11:15 AM <br />11:20 AM <br />Initial Reading (Rl): <br />10" <br />12" <br />Test End Time: <br />12:15 PM <br />12:20 PM <br />Final Reading (Rf): <br />10" <br />12" <br />Test Duration: <br />60 MIN. <br />60 MIN. <br />Chane in Reading (Rf-RI)-0- <br />-0- <br />Pass/Fail Threshold or <br />-0- Loss <br />-0- Loss <br />Criteria: <br />Test Results <br />VQ Pass 1 1 Fait <br />`1XI "Pass 1 =1 Fail : ' <br />1 I _! Pass I:' 1 Fail <br /># I Pass'�r a Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />SYSTEM PASSED <br />